Siemens SMART 7KT0311 Manual page 34

Multifunction meter
Table of Contents

Advertisement

Modbus register addresses list (Continued)
Hex
Address
Address
40033
0x21
Page sequence 17
40054
0x36
Page sequence 18
40055
0x37
Page sequence 19
40059
0x3B
Page sequence 20
40060
0x3C
Page sequence 21
40061
0x3D
Page sequence 22
40062
0x3E
Page sequence 23
40034
0x22
Demand Interval Method
40035
0x23
Demand Interval duration
40036
0x24
Demand Interval length
40057
0x39
Pulse Duration (Sec)
40058
0x3A
Pulse Weight (kWh)
40043
0x2B
Reset MAX current and power
40044
0x2C
Reset Energy mains
40046
0x2E
Reset ON hour
40047
0x2F
Reset Energy DI
Parameter
1 to 23
1 to 23
1 to 23
1 to 23
1 to 23
1 to 23
1 to 23
Min Value: 0x0000
Min Value: 0x0001
Min Value: 1
Min Value: 1
Min Value: 1
Min Value: 1
Min Value: 1
Min Value: 1
Min Value: 1
Min Value: 1
SMART 7KT0311 Manual
Range
1: First Page: 23: Last page
1: First Page: 23: Last page
1: First Page: 23: Last page
1: First Page: 23: Last page
1: First Page: 23: Last page
1: First Page: 23: Last page
1: First Page: 23: Last page
Meaning: Sliding
Meaning: Fixed
Max Value: 30
Max Value: 30
Max Value: 20
Max Value: 9999
Meaning: Reset all MAX Power and
Current
Meaning: Reset all mains energy to
factory setting range
Meaning: Reset ON Hour
Meaning: Reset all Dienergy to factory
setting range
Length
(Register)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
34