Conditions Power Supply; Conditions For Hydraulic System And Water Quality - Buderus Logano G115/3 WS Installation And Service Instructions Manual

Low-temperature oil boiler
Hide thumbs Also See for Logano G115/3 WS:
Table of Contents

Advertisement

2.8.5

Conditions power supply

Operating conditions
Power supply voltage
Circuit breaker
Frequency
Enclosure rating
Table 8 Power supply
2.8.6

Conditions for hydraulic system and water quality

Operating conditions
Operating pressure (above
atmospheric)
Permissible site test pressure
Safety temperature limitation by
TR temperature control
Safety temperature limitation by
manual reset high limit (STB)
Water quality
Table 9 System configuration and water quality
Logano G115 WS US/CA – 6 720 813 418 (2019/09)
120 V
Observe the voltage range of the burner and controls used. The outer casing/boiler must be
AC nominal
10 A
60 Hz
IP 40 (protected against contact by entry of foreign objects > 0.04 inches Ø
15 – 58 psi
45 – 75 psi
122 – 194 °F
210 °F
In combination with Beckett AquaSmart or Hydrolevel HydroStat the limit value (210 °F)
The heating system may only be filled and topped up with water of domestic water quality.
Notes – Requirement in greater detail
grounded for safety reasons and in order to function correctly.
(> 1 mm Ø ), no water proofing)
Notes – Requirement in greater detail
Maximum 30 psi with the supplied safety valve.
may not be exceeded.
We recommend a pH value of 8.2 – 9.5.
2
Product description
11