Safety Requirements
Table A-1 Withstand voltage test
Test Point
Minimum Test
Voltage
Input and PE
2500 V DC
1500 V AC
Input and
4242 V DC
output
Output and PE
SGND of the 12 V output and the PE are short-circuited inside the PSU.
Leakage current
0.75 mA (230 V AC/60 Hz), 0.875 mA (264 V AC/60 Hz)
Insulation
≥ 10 megohms. The insulation resistance of the primary circuit to the
resistance
secondary circuit and that of the primary circuit to PE should be at least 10
megohms in the following conditions: V
(non-condensing)
Input to output must meet the reinforced insulation requirements after the output ground is disconnected from
the PE.
Technical Manual
Test Duration
1 minute
1 minute
1 minute
Leakage
Expected Result
Current
≤ 10 mA
No breakdown or
arcing
≤ 10 mA
No breakdown or
arcing
≤ 10 mA
No breakdown or
arcing
= 500 V DC; relative humidity < 90%