PAC3000S12-T1 PSU
240HVDC input
Parameter
Input overvoltage
protection threshold
Input overvoltage recovery
threshold
Input undervoltage
protection threshold
Input undervoltage
recovery threshold
PFC overvoltage protection
1. If input overvoltage or undervoltage protection is triggered, both MV12 and MV6 are shut down. The input
voltage threshold that causes MV12 to shut down is the same as the input voltage threshold that causes
MV6 to shut down.
2. If input overvoltage or undervoltage is rectified, both MV12 and MV6 recover. The input voltage threshold
that causes MV12 to recover is the same as the input voltage threshold that causes MV6 to recover.
Output
Parameter
Output
Output overvoltage
MV12
protection
MV6
SV12
Technical Manual
Minimum
Typical
310
-
305
-
-
-
-
-
-
-
Minimum
Typical
13
-
13
-
13
-
2 Electrical Specifications
Maximum
Unit
Notes & Conditions
-
V
Self-recovery
Hysteresis ≥ 5 V
-
V
175
V
Self-recovery
Hysteresis ≥ 5 V
180
V
-
-
PFC overvoltage does
not damage the bus
capacitor (excluding
damage caused by
input overvoltage).
Maximum
Unit
15
V
15
V
15
V
15
Notes &
Conditions
Latch-off mode
Latch-off mode
In the MV6 mode, if
the PSU loop is
detected to be
open, protection is
triggered directly
without having to
reach the MV6
overvoltage
protection
threshold.
Latch-off mode