7 - POSITIONING AND INSTALLATION
Side view after installation on roof (position C):
Standard roofcurb
E
C
A
D
β
β
Dimensions (mm)
A
020 to 047
472
Standard
052 to 062
510
roofcurb
070 to 099
486
Burner roofcurb
E
C
A
D
β
β
Dimensions (mm)
A
020 to 047
782 750 103 679
Burner
052 to 062
822 750 103 719
roofcurb
070 to 099
855 752 103 752
Important: Check that the roofcurb height is suffi cient to respect
the minimum sealing height required according to local regulations
(example: 150 mm minimum sealing height in France according
to DTU).
To do this, check that the "D" dimension of the roofcurb exceeds
the thickness of the roof plus the insulation plus the minimum
sealing distance required.
50FF/FC unit
D
Roofcurb
16
= maximum slope
B
C
D
E
440
103
369
34
440
103
407
34
440
103
383
34
= maximum slope
B
C
D
E
F
34
490 3º (5,1%)
34
490 3º (5,5%)
34
490 2º (4,0%)
Sealing
upsweep
150mm min.
Insulation
Joist
Steel pan
Air ducts connections
For units with vertical airfl ow, the ducts must be connected to the
profi les from underneath the roofcurb.
In order to carry out the air ducts follow the recommendations in
the paragraph 9.4 "Air ducts connections".
The thickness of the sheet metal profi les to connect the discharge
B
and/or return ducts to the roofcurb are shown in the following
tables:
Standard roofcurb
β
3º (5,1%)
3º (5,5%)
2º (4,0%)
F
B
Dimensions (mm)
020 to 047
Standard
052 to 062
roofcurb
β
070 to 099
Burner roofcurb
Dimensions (mm)
020 to 047
Burner
052 to 062
roofcurb
070 to 099
A
B
C
50
798
321
619
50
1234
470
745
50
1575
470
715
A
B
C
D
E
F
G
50 797 373 0 275 631 52 155 770 89
50 1229 470 376 207 619 85 155 1219 101
50 1570 470 373 126 704 85 155 1491 198
D
E
243
410
410
H
I
J