MODEL 30 CONTROLLER - INSTALLATION AND OPERATIONS GUIDE
Steps To Perform Provisioning Service
1. Navigate to the ProvisioningNiagara palette, add a new NetworkJobPrototype to any place in the
station under Config (NiagaraNetwork for example) and name the job prototype (example -
CIPer30_1.1.4_Upgrade).
NOTE
Make sure to increase the Device Reboot Timeout from 10 minutes to 15 minutes if you are
connecting more than 6 expansion IO to the CIPer Model 30 controller.
2. Click the (+) icon from Steps run for each station section, select Upgrade Out-of-date Software, and
then click OK.
You can view the list of jobs defined for the required stations.
3. Click the (+) icon from Stations to include in the job section, select the checkbox to select a specific
station, or select the Check All option to select the all listed station, and then click OK.