Carrier XCT 7 Series Installation And Owner's Manual page 28

Two- way console
Hide thumbs Also See for XCT 7 Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
Electrical Wiring
Dipswitch setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF.
Definition principles of code switches:
SW01 is used to set the capabilities of the master and slave indoor units as well as the indoor unit; SW03 is used to set
the address of the indoor unit (combine original communication address and address of centralized controller).
(A) Definition and description of SW01
Address of
SW01_1
wire
SW01_2
controlled
SW01_3
indoor unit
(group
SW01_4
address)
SW01_5
Capability of
SW01_6
indoor unit
SW01_7
SW01_8
Note : A wired controller can connect to at most sixteen ultrathin air-duct indoor units.
[1]
[2]
[3]
[4]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
...
...
.. .
.. .
1
1
1
1
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
Address of wire controlled indoor unit (group
address)
0# (wire-controlled master unit) (default)
1# (wire-controlled slave unit)
2# (wire-controlled slave unit)
3# (wire-controlled slave unit)
15# (wire-controlled slave unit)
Capability of indoor unit
0.6HP
0.8HP
1.0HP
1.2HP
1.5HP
1.7HP
2.0HP
2.5HP
3.0HP
3.2HP
4.0HP
5.0HP
6.0HP
8.0HP
10.0HP
15.0HP
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents