ECO-MODE SWITCH
This generator is equipped with an Eco-Mode Idle Control Switch
(Fig. 22). Engaging this switch allows the system to regulate the
engine speed and automatically adjust its fuel consumption to
match the required load. When the electrical load changes, the
generator engine will automatically speed up and slow down as
needed. This reduces fuel consumption and noise levels, while
extending runtime and engine's lifespan.
Keep this switch engaged ONLY when the power load requirement is less than 2400W. Do not engage the Eco-Mode
Switch when the total load is more than 2400W. The generator engine must run at full speed to supply power for
anything over 2400W.
PARALLEL OPERATION
The parallel connection ports (Fig. 23) allow you to connect two
WEN generators to increase the total available electrical power.
The WEN Parallel Connection Kit can be purchased from
wenproducts.com. Follow the instructions included with your
parallel connection kit for proper installation and operation.
IN CASE OF OVERLOAD
If your generator becomes overloaded from too much drawn
wattage, the overload indicator (red) on the control panel will
light up. Follow the instructions below when an overload occurs:
• When you're close to overloading the generator, the overload
light will start to flash. Reduce the load by turning off and dis-
connecting your electronic device(s) until the overload light turns
off. Then you may continue to operate your generator.
• When you've overloaded the generator, the overload light will stay on and the reset button (Fig. 24) will activate
to cut off the output in 3 to 16 seconds, depending on the load. Reduce the load by turning off and disconnecting
your electrical device(s) until the overload light turns off. Wait about five minutes and then press the activated reset
button to reset the circuit. If no power is produced after resetting, turn off and disconnect all electrical devices and
restart your generator.
LIGHT
GREEN (POWER INDICATOR)
ON
ON
OFF
OFF
OFF
OFF
OFF
USING YOUR GENERATOR
RED (OVERLOAD)
OFF
Flashing Continuously
Flashes 1x
Repeating every 3 seconds
Flashes 2x
Repeating every 3 seconds
Flashes 3x
Repeating every 3 seconds
Flashes 5x
Repeating every 3 seconds
Flashes 6x
and cut off power to protect itself. No
Repeating every 3 seconds
MEANING
Generator output is normal.
Generator is exceeding rated output.
Voltage at alternator is too low.
No electrical output.
Engine speed is too low.
No electrical output.
Inverter temperature is too high. No
electrical output.
Voltage at alternator is too high.
No electrical output.
Generator has exceeded rated output
electrical output.
ON
OFF
ECO-MODE
RESOLUTION
No action needed.
Reduce load on generator.
Check for loose connections.
Call 1-800-232-1195 for assistance.
Check carburator and stepper motor.
Ensure Eco-Mode is OFF. Have genera-
tor serviced; call 1-800-232-1195 for
assistance.
Turn generator off and let cool down fully
(1-2 hours) before restarting.
Have generator serviced; call
1-800-232-1195 for assistance.
Turn OFF and disconnect loads. Press
RESET button on panel.Reduce load on
generator.