Clearances - Empire Comfort Systems Deluxe VFD32FB0L-3 Installation Instructions And Owner's Manual

Vent-free universal fireboxes
Table of Contents

Advertisement

Sidewall clearances: The clearance from the inside of the firebox
to perpendicular combustible side wall should not be less than
6 inches. See Figure 1.
Firebox Side and Back Clearances: The firebox outer casing side
and back flanges are zero clearance to combustibles.
Top Framing and Finishing: Combustible finishing materials
requires 3/4 inch to top of unit. See Figure 2.
FRONT FACE (SIDE)
Page 4

cLEARANcES

COMBUSTIBLE
MATERIALS ALLOWED
IN SHADED AREAS
FIREBOX
(TOP VIEW)
3"
MAX.
45°
6"
PERPENDICULAR
SIDE WALL
Figure 1
2 X 4
HEADER
Figure 2a - Louvered Models
2 X 4
HEADER
Figure 2b - Flush Models
COMBUSTIBLE
FINISHED WALL
OR MANTEL
FINISHED WITH
TRIM KIT OR
NON-COMBUSTIBLE
MATERIAL
3/4" GAP REQUIRED
COMBUSTIBLE
FINISHED WALL
OR MANTEL
3/4" GAP REQUIRED