Process connection Fig. 2: Type plate 1.3 Intended use The DS34 is a differential pressure switch for overpressure, underpressure and differential pressure measurements. The uncomplicated and robust membrane measuring mechanism is suitable for all neutral media, such as service water, heating water, neutral gases and oils.
2 | Assembly and Starting Operation FISCHER Mess- und Regeltechnik GmbH 2 Assembly and Starting Operation 2.1 General The device is intended for installation on flat walls and mounting plates. The device can be equipped with a mounting foot for screwing to the mounting plate.
FISCHER Mess- und Regeltechnik GmbH Assembly and Starting Operation | 2 2.4 Start-up 2.4.1 General A prerequisite for commissioning is correct installation of all electrical supply lines and the differential pressure lines. All connections are arranged so that there are no mechanical forces acting on the device.
3 | Servicing FISCHER Mess- und Regeltechnik GmbH 3 Servicing 3.1 Maintenance The instrument is maintenance-free. We recommend the following regular in- spection to guarantee reliable operation and a long service life: • Check the function in combination with downstream components.
FISCHER Mess- und Regeltechnik GmbH Technical data | 4 4 Technical data 4.1 General Reference conditions (acc. to IEC 61298-1) Temperature +15 to +25 °C Relative humidity 45 … 75 % Air pressure 86 to 106 kPa 860 to 1060 mbar...
4 | Technical data FISCHER Mess- und Regeltechnik GmbH 4.6 Operating conditions Ambient temperature range -10 to +70 °C Storage temperature range -10 to +80 °C Medium temperature range -10 to +80 °C (for non-freezing media) Low-Voltage Directive EN 61010-1:2010 + A1:2019 +...
5 | Order codes FISCHER Mess- und Regeltechnik GmbH 5 Order codes Reference No. 10 11 12 Type [1,2] Setting range Measuring range 0.06 … 0.6 bar 0 … 0.6 bar 0.10 … 1.0 bar 0 … 1 bar 0.16 … 1.6 bar 0 …...