Convenience Outlets; Non-Powered Type; Unit-Powered Type; Wet In Use Convenience Outlet Cover - Carrier WeatherMaker 50TC 17-30 Series Service And Maintenance Instructions

Single package rooftop unit with electric cooling and optional electric heat with puron (r-410a) refrigerant
Table of Contents

Advertisement

CONVENIENCE OUTLETS

WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or
death.
Units with convenience outlet circuits may use multiple
disconnects. Check convenience outlet for power status before
opening unit for service. Locate its disconnect switch, if
appropriate, and open it. Lock-out and tag-out this switch, if
necessary.
Two types of convenience outlets are offered on 50TC models:
non-powered and unit-powered. Both types provide a 125-v
Ground-Fault Circuit-Interrupter (GFCI) duplex receptacle rated
at 15A behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 33.
CONVENIENCE
OUTLET GFCI
Fig. 33 — Convenience Outlet Location

Non-Powered Type

This type requires the field installation of a general-purpose 125-v
15A circuit powered from a source elsewhere in the building. Ob-
serve national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and location.
Route 125-v power supply conductors into the bottom of the utili-
ty box containing the duplex receptacle.

Unit-Powered Type

A unit-mounted transformer is factory-installed to stepdown the
main power supply voltage to the unit to 115-v at the duplex re-
ceptacle. This option also includes a manual switch with fuse, lo-
cated in a utility box and mounted on a bracket behind the conve-
nience outlet; access is through the unit's control box access panel.
See Fig. 34 for wiring.
DUTY CYCLE
The unit-powered convenience outlet has a duty cycle limitation.
The transformer is intended to provide power on an intermittent
basis for service tools, lamps, etc. It is not intended to provide
15 amps loading for continuous duty loads (such as electric heat-
ers for overnight use). Observe a 50% limit on circuit loading
above 8 amps (i.e., limit loads exceeding 8 amps to 30 minutes of
operation every hour).
The primary leads to the convenience outlet transformer are not
factory-connected. Selection of primary power source is a custom-
er option. If local codes permit, the transformer primary leads can
be connected at the line-side terminals on a unit-mounted non-
fused disconnect or circuit breaker switch; this will provide
PWD-CO TRANSFORMER
PWD-CO FUSE
SWITCH
CONTROL BOX
ACCESS PANEL
service power to the unit when the unit disconnect switch or cir-
cuit breaker is open. Other connection methods will result in the
convenience outlet circuit being de-energized when the unit dis-
connect or circuit breaker is open. See Fig. 34.
UNIT
CONNECT
VOLTAGE
AS
208,230
240
460
480
575
600
Fig. 34 — Powered Convenience Outlet Wiring

Wet in Use Convenience Outlet Cover

The unit has a "wet in use" convenience outlet cover that must be
installed on the panel containing the convenience outlet. This cov-
er provides protection against moisture entering the GFCI recepta-
cle. This cover is placed in the unit control box during shipment.

GFCI Maintenance

Periodically test the GFCI receptacle by pressing the TEST button
on the face of the receptacle.
1.
Press the TEST button on the face of the receptacle. This
should cause the internal circuit of the receptacle to trip and
open the receptacle.
2.
Check for proper grounding and power line phasing should
the GFCI receptacle fail to trip.
25
PRIMARY
TRANSFORMER
CONNECTIONS
TERMINALS
L1: RED +YEL
H1 + H3
L2: BLU + GRA
H2 + H4
L1: RED
H1
Splice BLU + YEL
H2 + H3
L2: GRA
H4
L1: RED
H1
L2: GRA
H2

Advertisement

Table of Contents
loading

Table of Contents