Trns 9 Return Code - Hitachi EH-150 Series Applications Manual

Table of Contents

Advertisement

A.5

TRNS 9 Return code

The return code of TRNS 9 command and error factors are shown in the following table.
Error
No.
Item
code
1
HFF
CPU error
2
(None)
Watch dog timer error
3
H03
OS system error
4
H21
Range check error
Sending data area setting
5
H22
error
Sending data area range
6
H23
error
Receiving data area
7
H24
setting error
Receiving data area
8
H25
range error
9
H28
Area overlap error
10
H30
Command time-out error
11
H40
Receiving data overflow
Designated Invalid
12
H50
command
13
H51
Number of entries over
14
H81
Command not-supported
15
H82
Initial setting error
16
H83
Transmission data error
17
H84
Receive buffer full
18
H85
Connect error
When EH-SIO detects serious failure, EH-SIO stops operation.
A gray cell is the error which CPU detects.
Table A.13 TRNS 9 Return code ( 1 / 2 )
Error
level
---
Since error occurred in CPU, EH-SIO also stopped operation.
Serious
MPU of EH-SIO stops having operated as the system program,
error
and detected the abnormalities in MPU by the watch dog timer.
Serious
The system OS of EH-SIO detected errors.
error
Warning
The last address of s, t parameter is over the range of I/O.
Warning
The head address of sending data area is not right.
Warning
The last address of sending data area is over the range of I/O.
Warning
The head address of receiving data area is not right.
Warning
The last address of receiving data area is over the range of I/O.
Area has overlapped. (s parameter, t parameter, sending data area,
Warning
receiving data area)
Warning
TRNS 9 command was not completed within the specified time.
Warning
Receiving data was not able to store in receiving data area.
TRNS 9 was executed to the port used as the slave function or the
Warning
simple data link function.
- Slot number is wrong.
Warning
- The number of slave function or simple-link function is over the
max. number.
- Command not supported.
Warning
- Initializing duplicates.
- Parameter error in initializing
Warning
- Initializing incomplete
Warning
Parameter error
The input buffer of EH-SIO is filled with the receiving data which is not
Warning
read by CPU.
Since DR signal from external device is OFF, data cannot be
Warning
transmitted.
A - 29