Hitachi EH-150 Series Applications Manual page 194

Table of Contents

Advertisement

Appendix
Error
No.
code
19
H8A
Parity error
20
H8B
Framing error
21
H8C
Overrun error
22
H8D
Check code error
23
H8E
Timeout error (Receive)
24
H8F
Timeout error (Send)
25
H90
Error message reception
26
H91
Message data error
Designated query error
27
H92
(Modbus mode)
Table A.14 TRNS 9 Return code ( 2 / 2 )
Error
Item
level
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Warning
Parity error in receiving data.
Framing error in receiving data.
Overrun error in receiving data.
Check code error in receiving data.
Reception of data was not completed within the time specified by
EH-SIO.
EH-SIO did not complete transmission of data by within the
time interval.
(Monitoring time is fixed by the system. It cannot be changed.)
Error message response was received.
(Example: Modbus exception response reception, etc.)
A message containing inaccurate data was transmitted and received.
(Example: The wording is correct as a telegram message,
but the contents of the data are abnormal ASCII data.)
Sent data (query) format is wrong.