Orbis ALPHA - Time Switch Manual

Orbis ALPHA - Time Switch Manual

Advertisement

Orbis ALPHA - Time Switch Manual

OVERVIEW

Overview

FIG.1

  1. Transparent protection cover.
  2. Alpha module.
  3. Plastic frame for 72x72 flush mounting.
  4. Plastic bracket for 72x72 flush mounting.
  5. Base with connection terminals for DIN or wall mounting.
  6. Terminal cover.

DESCRIPTION

Control device with independent mounting for wall mounting, panel or 35 mm rail, in accordance DIN EN 60715.

The ALPHA time switch controls any electrical installation by means of daily (D and QRD) or weekly (S and QRS) programs.

INSTALLATION

warningATTENTION:
Electrical devices must be installed and assembled by an authorized installer.
Loosen the screws to remove the clock base.
Connect the wires according to the FIG.2 connection scheme.

PROGRAMME

For setting the programme, move the pins to IN or OUT position. As the pins activate a changeover contact, consider that the pins in OUT position close the contact between terminal 1 and 3 on the IN position terminal 2 and 3.

HOUR UPDATING

Turn the dial by moving the minute dial.

MANUAL OVERRIDE

A = Auto. Time programmed.
O = Off. Permanently off (output terminal 2).
I = On. Permanently on (output terminal 1).

TECHNICAL CHARACTERISTICS

Supply voltage Follow the indications
Switching capacity 16(4) A 250 V ~
Type of action 1B, 1T, 1U, 1R (D and S)
1B, 1T, 1U, 1S (QRD and QRS)
Power consumption 0,8 W
Operating accuracy D and S: Depending on line frequency
QRD and QRS: ± 1 sec/day at 23º C
Power reserve D and S: without reserve
QRD and QRS: 100 hours after uninterrupted supply of 48 hours
Type of dial Daily: 96 pins
Weekly: 84 pins
Minimum switching time Daily: 15 minutes
Weekly: 2 hours
Operating accuracy Daily: ± 5 minutes
Weekly: ± 10 minutes
Operating temperature -10º C to +50º C
Operating category IP 20 as per EN 60529
Protection class II under correct assembling conditions
Pollution situation 2

warningATTENTION:
This unit incorporates a battery which contents can be harmful to the environment. Please do not throw it away without removing the battery and putting it in the proper container for recycled batteries or to send the complete unit back to the factory.

ORBIS TECNOLOGÍA ELÉCTRICA, S.A.
Lérida, 61 E–28020 MADRID
Teléfono: + 34 91 5672277;
Fax: +34 91 5714006
E-mail: info@ orbis.es
http://www.orbis.es

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Orbis ALPHA - Time Switch Manual

Advertisement

Need Assistance?

Do you have a question about the ALPHA that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents