AXFP 22-140 AVD Always read before installation. Aisin INDOOR UNITS INSTALLATION AND MAINTENANCE INSTRUCTIONS [ Model ] Round Flow Cassette Applicable models AXFP22AVD AXFP56AVD AXFP28AVD AXFP71AVD AXFP36AVD AXFP90AVD AXFP45AVD AXFP140AVD Important reminder - THOROUGHLY READ THESE INSTRUCTIONS BEFORE STARTING THE INSTALLATION AND FOLLOW ALL PROCEDURES DESCRIBED WITHIN.
Installation AXFP22AVD AXFP45AVD AXFP90AVD Gas driven heat pumps air conditioners AXFP28AVD AXFP56AVD AXFP112AVD and operation manual AXFP36AVD AXFP71AVD AXFP140AVD Precautions ONTENTS Page This appliance is not intended for use by persons, including ■ Before installation................1 children, with reduced physical, sensory or mental capabilities, Important information regarding the refrigerant used......
Optional accessories For this unit you can select different air flow directions. It is necessary to purchase an optional blocking pad kit to discharge the air in 3 or ■ There are two types of remote controllers: wired and wireless. 4 (closed corners) directions.
Apply the long side of the Air flow directions as shown in figure 1 merely NOTE installation guide after removal serve as examples of possible air flow directions. of the tear-off tab in case of installation with self cleaning decoration panel Use suspension bolts for installation.
■ To prevent water leakage, execute heat insulation work NDOOR UNIT INSTALLATION completely on both sides of the gas and liquid piping. When using a heat pump, the temperature of the gas piping can reach When installing optional accessories (except for the decoration up to approximately 120°C, use insulation which is sufficiently panel), read also the installation manual of the optional accessories.
Piping insulation procedure RAIN PIPING WORK Gas piping Liquid piping Installation of drain piping Install the drain piping as shown in figure and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings. 1-1.5 m Piping insulation material (field supply) Flare nut connection...
■ How to perform piping (See figure 7) Do not touch the drain pump. It may result in electric shock. Ceiling slab Control box lid Hanger bracket Power supply wiring Adjustable range Power supply terminal block Drain raising pipe (nominal diameter of vinyl pipe = 25 mm) Clamp (field supply) Drain hose (supplied with the unit) Unit transmission wiring...
Electrical characteristics Precautions Observe the notes mentioned below when wiring to the power Model Volts Voltage range supply terminal block. min. 198-max. 264 / Use a round crimp-style terminal for insulation sleeve for AXFP22~140 50 / 60 220-240/220 min. 198-max. 242 connection to the terminal block for wiring the units.
Summary of field settings IRING EXAMPLE Fit the power supply wiring of each unit with a switch and fuse as Mode First Second code No. (Note 2) code shown in figure (Note 1) No. Description of setting Filter contamination Power supply - Heavy/Light = Setting to define Main switch...
Control by 2 Remote Controllers (Controlling 1 indoor EST OPERATION unit by 2 remote controllers) Refer to the installation manual of the outdoor unit. When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB". NOTE When performing field settings or test operation without attaching the decoration panel, do not touch...
How to clean the air outlet and outside panels Open the suction grille (See figure 21) (action illustration). ■ Clean with a soft cloth. Push both levers simultaneously in the direction of the arrow as indicated in the illustration and carefully lower the grille. ■...