Figure 7-3 I/O-Expander 201OPT with pump and fan control (Modbus)
NOTE! Termistor input (terminals 327 and 328) must be shorted if not used.
READY = ON, when mains voltage has been applied and Vacon CX is ready to operate.
RUN = ON, when motor is running.
FAULT = ON, if a fault occurs.
Vacon Plc
Phone: +358-201 2121
Service: +358-40-8371 150
Pump and fan control with autochange
Terminal
Signal
301
DID1
Interlock input,
autochange 1
302
DID2
Interlock input
autochange 2
303
DIE3
Interlock input,
autochange 3
304
DIE4
Interlock input
autochange 4
305
COMD
Common for DID1-DID2
306
+24 V
Control voltage output
307
COME
Common for DIE3-DIE4
308
GND
I/O ground
309
DID5A+ Interlock input
310
DID5A-
autochange 5
311
DID6B+
312
DID6B-
313
DID7Z+
314
DID7Z-
315
GND
I/O ground
316
DOD1
Open collector output 1
317
DOD2
Open collector output 2
318
DOD3
Open collector output 3
319
DOD4
Open collector output 4
320
GND
I/O ground
327
TI+
Termistor input
328
TI-
Fax:+358-201 212 205
E-mail: vacon@vacon.com
Vacon
Description
Contact closed = interlock is active
Contact closed = interlock is active
Contact closed = interlock is active
Contact closed = interlock is active
Connect to GND or +24 V
Voltage for switches, etc. max. 0.1 A
Connect to GND or +24 V
Ground for reference and controls
Contact closed = interlock is active
Ground for reference and controls
Aux. drive 1 / autochange 1 control
Aux. drive 2 / autochange 2 control
Aux. drive 3 / autochange 3 control
Fieldbus control
Ground for reference and controls