Haier AP48KN1EAA Service Manual page 37

Commercial air conditioning
Table of Contents

Advertisement

Type 1: Standard defrost
(1) If Tr≥-2℃ , when Tp≤-6℃ , enter defrost.
(2) If -12℃ ≤Tr < -2℃ , when Tp≤-6℃ , please refer to the following chart.
(3) No matter the ambient temperature, when Tp≤-16℃ , enter defrost.
Type 2: Non-standard defrost (rectify defrost data by the device)
(1) If Tr≥6℃ , when Tp≤-6℃ , enter defrost.
(2) If -18℃ ≤Tr < -6℃ , when Tp≤-6℃ , please refer to the following chart.
(3) No matter the ambient temperature, when Tp≤-18℃ , enter defrost.
Single Split
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ap48kn1eaah1u48in1eab

Table of Contents