Haier AP48KN1EAA Service Manual page 19

Commercial air conditioning
Table of Contents

Advertisement

Installation procedures
Installation of indoor unit
Selection of installation place
Place where it is easy to route drainage pipe and outdoor piping.
Place away from heat source and with less direct sunlight.
Place where cool and warm air could be delivered evenly to every corner of the room.
Place near power supply socket. Leave enough space around the unit (refer to installation
drawings).
Fixing of the unit
1.Position of the wall hole
Wall hole should be decided according to installtion place and piping direction. (refer to
installation drawings)
2.Making a wall hole
Drill a hole of 70mm dia. with a little
slope towards outside.
Install piping hole cover and seal it
with putty after installation.
Fixing of indoor unit
With the unit set up vertically,fix the fitting metal to the unit with screws, then fix
the fitting metal to the wall with cement nail and washer, as shown below:
Moreover, if want to fix the unit more firmly, you should fix the bottom panel to
the ground with concrete bolts,as shown below:
Fitting hole
Cement nail
Screw
4- 14 hole 30 depth
Bottom Panel
Single Split
INDOOR SIDE
wall hole
70mm
( Cross section of wall hole )
Fitting metal
330
260
17
OUTDOOR SIDE
wall thickness
2- 10 hole
130

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ap48kn1eaah1u48in1eab

Table of Contents