13. Installation
AJ080TXJ4KG
A-unit
1(L) 2(N) F1
1 2
1
2
Earth
terminal
Cable Type : A
A
Cable Type : B
B
Cable Type : C
C
Specification for circuit breaker and power supply cord
• Power supply cord is not supplied with air conditioner.
• Select the power supply cord in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power supply cord and branch wiring are in compliance with local cord.
Model
Outdoor Unit
Indoor Unit
AJ040TXJ2KG
AJ050TXJ2KG
AJ052TXJ3KG
AJ068TXJ3KG
AJ080TXJ4KG
NOTE
1. Power Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F , IEC:60245 IEC 66 / CENELEC: H07RN-F )
2. Select power supply cord based on MCA.
3. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
4. MCA represents maximum input current.
5. MFA represents capacity which may accept MCA.
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)
※ In case you want more information about the controllers and accessories, please refer to the Controller and Accessory TDB
on pvi.Samsung.com site or Global Partner Portal site.
B-unit
F2
1(L) 2(N) F1
1 2
F1 F2
Earth
Earth
terminal
terminal
C
B
1
2
F1 F2
Earth
terminal
1(L) 2(N) 1(L) 2(N)
Power cable to indoor units
Outdoor Units
Rated
Hz
2 Room
50
1phase,220-240
2 Room
50
1phase,220-240
3 Room
50
1phase,220-240
3 Room
50
1phase,220-240
4 Room
50
1phase,220-240
C-unit
Indoor unit
F2
1(L) 2(N) F1
Assembly cable
1 2
F1 F2
Earth
terminal
C
B
1
2
F1 F2
Earth
terminal
Outdoor unit
Main Power
Supply cable
L
N
1
2
Earth
terminal
A
Maximum Input Current[A]
Outdoor
Volts
8.5
11.0
11.0
16.6
16.6
Screw
M4
D-unit
F2
1(L) 2(N) F1
F2
1 2
F1 F2
F1 F2
Earth
terminal
C
B
C
1
2
F1 F2
F1 F2
Earth
terminal
F1 F2 F1 F2
Communication cable
to indoor units
Indoor(Max.)
Total
0.8
9.3
0.8
11.8
1.2
12.2
1.2
17.8
1.6
18.2
Tighten Torque(kgf.cm)
12.0~18.0
Power Supply
MCA
MFA
9.30
10.63
11.80
13.75
12.20
13.75
17.80
20.75
18.20
20.75
Position
1(L),2(L),L,N,F1,F2
309