LG MULTI V WATER IV ARWN LAS4 Series Service Manual page 7

Outside unit

Advertisement

System Capacity
Model Name
Cooling
Capacity
Heating
Cooling
Input
Heating
Casing Color
Type
Combination
Piston Displacement
Number of revolution
Compressor
Motor Output
Starting Method
Oil Type
Oil Charge Amount
Type
Maximum Pressure Resistance
Heat Exchanger
Head Loss
Rated Water Flow
Temp. range of
Cooling
Circulation water
Heating
Refrigerant
Liquid
Connecting Pipes
Gas
Water
Inlet
Connecting
Outlet
Pipes
Drain Outlet
Dimensions(WxHxD)
Net Weight
Cooling
Sound Pressure
Level
3)
Heating
Sound Power
Cooling
Level
4)
Heating
Transmission Cable(CVV-SB)
Name
Refrigerant
Control Device
Power Supply
Notes:
1. Capacities and Inputs are based on the following conditions
Cooling : Indoor temp. 27°C [80.6°F]DB/19°C[66.2°F]WB
Water inlet temp. 30°C[86°F]
Heating : Indoor temp. 20°C[68°F]DB
Water Inlet temp. 20°C[68°F]
* Interconnecting Piping Length 7.5m (25 ft.)
* Level Difference of Zero
2. Capacities are net capacities.
3. Sound pressure level is measured on the rated condition in the anechoic
rooms by ISO 3745 standard.
HP
32
Combination Unit
ARWN320LAS4
ARWN180LAS4
Independent Unit
ARWN140LAS4
kW
89.6
kcal/h
77,000
Btu/h
305,800
kW
100.8
kcal/h
86,700
Btu/h
344,000
kW
17.53
kW
18.30
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 2
cm
3
/rev
43.8 + 62.1
rev/min
Inverter 3,600 at 60Hz
kW
4.2 + 5.3
Direct On Line
FVC68D(PVE)
cc
1,400 + 1,200
Stainless Steel Plate
kgf/cm
2
45
kPa
24 + 29
LPM
173 + 135
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
mm(inch)
19.05(3/4)
mm(inch)
34.9 (1-3/8)
mm
PT 40 + PT 40
mm
PT 40 + PT 40
mm
20
mm
(755 × 997 × 500) x 2
inch
(29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2
kg
(140 x 1) + (127 x 1)
lbs
(309 x 1) + (280 x 1)
dB(A)
59
dB(A)
58
dB(A)
72
dB(A)
71
mm
2
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
V, Ø, Hz
380, 3, 60
4. Sound power level is measured on the rated condition in the reverbera-
5. Wiring cable size must comply with the applicable local and national code.
6. Due to our policy of innovation some specifications may be changed
7. Add an anti freeze to circulation water when outside units is operating
- 7 -
34
ARWN340LAS4
ARWN200LAS4
ARWN140LAS4
95.2
81,900
324,900
107.1
92,100
365,500
19.04
19.84
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 2
43.8 + 62.1
Inverter 3,600 at 60Hz
4.2 + 5.3
Direct On Line
FVC68D(PVE)
1,400 + 1,200
Stainless Steel Plate
45
30 + 29
192 + 135
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
19.05(3/4)
34.9 (1-3/8)
PT 40 + PT 40
PT 40 + PT 40
20
(755 × 997 × 500) x 2
(140 x 1) + (127 x 1)
(309 x 1) + (280 x 1)
59
61
72
74
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
380, 3, 60
tion rooms by ISO 3741 standard.
without prior notification.
under 10℃(50°F), and change the DIP switch on main PCB. (For more
information, refer a installation manual.)
Copyright © 2013 - 2019 LG Electronics Inc.
All rights reserved. Only training and service purposes.
Specification
[50Hz/60Hz]
36
ARWN360LAS4
ARWN180LAS4
ARWN180LAS4
100.8
86,600
344,000
113.4
97,600
387,000
19.38
20.26
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 2
62.1 + 62.1
Inverter 3,600 at 60Hz
5.3 + 5.3
Direct On Line
FVC68D(PVE)
1,400 + 1,400
Stainless Steel Plate
45
24 + 24
173 + 173
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
19.05(3/4)
41.3(1-5/8)
PT 40 + PT 40
PT 40 + PT 40
20
(755 × 997 × 500) x 2
140 x 2
309 x 2
56
57
69
70
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
380, 3, 60