Outside unit

Advertisement

Specification
System Capacity
Model Name
Cooling
Capacity
Heating
Cooling
Input
Heating
Casing Color
Type
Combination
Piston Displacement
Number of revolution
Compressor
Motor Output
Starting Method
Oil Type
Oil Charge Amount
Type
Maximum Pressure Resistance
Heat Exchanger
Head Loss
Rated Water Flow
Temp. range of
Cooling
Circulation water
Heating
Refrigerant
Liquid
Connecting Pipes
Gas
Inlet
Water
Connecting
Outlet
Pipes
Drain Outlet
Dimensions(WxHxD)
Net Weight
Sound Pressure
Cooling
Level
3)
Heating
Sound Power
Cooling
Level
4)
Heating
Transmission Cable(CVV-SB)
Name
Refrigerant
Control Device
Power Supply
Notes:
1. Capacities and Inputs are based on the following conditions
Cooling : Indoor temp. 27°C [80.6°F]DB/19°C[66.2°F]WB
Water inlet temp. 30°C[86°F]
Heating : Indoor temp. 20°C[68°F]DB
Water Inlet temp. 20°C[68°F]
* Interconnecting Piping Length 7.5m (25 ft.)
* Level Difference of Zero
2. Capacities are net capacities.
3. Sound pressure level is measured on the rated condition in the anechoic
rooms by ISO 3745 standard.
HP
62
Combination Unit
ARWN620LAS4
ARWN200LAS4
ARWN200LAS4
Independent Unit
ARWN120LAS4
ARWN100LAS4
kW
173.6
kcal/h
149,400
Btu/h
592,300
kW
195.3
kcal/h
168,000
Btu/h
666,500
kW
33.95
kW
35.43
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 4
cm
3
/rev
62.1 + 62.1 + 43.8 + 43.8
rev/min
Inverter 3,600 at 60Hz
kW
5.3 + 5.3 + 5.3 + 5.3
Direct On Line
FVC68D(PVE)
cc
1,400 + 1,400 + 1,200 + 1,200 1,400 + 1,400 + 1,200 + 1,200 1,400 + 1,400 + 1,200 + 1,200
Stainless Steel Plate
kgf/cm
2
45
kPa
30 + 30 + 22 + 16
LPM
192 + 192 + 116 + 96
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
mm(inch)
22.2(7/8)
mm(inch)
44.5(1-3/4)
mm
PT 40 + PT 40 + PT 40 + PT 40
mm
PT 40 + PT 40 + PT 40 + PT 40
mm
20
mm
(755 × 997 × 500) x 4
inch
(29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4 (29-23/32 x 39-1/4 x 19-11/16) x 4
kg
(140 x 2) + (125 x 2)
lbs
(309 x 2) + (276 x 2)
dB(A)
59
dB(A)
63
dB(A)
73
dB(A)
77
mm
2
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
V, Ø, Hz
380, 3, 60
4. Sound power level is measured on the rated condition in the reverbera-
5. Wiring cable size must comply with the applicable local and national code.
6. Due to our policy of innovation some specifications may be changed
7. Add an anti freeze to circulation water when outside units is operating
- 12 -
64
ARWN640LAS4
ARWN200LAS4
ARWN200LAS4
ARWN120LAS4
ARWN120LAS4
179.2
154,200
611,400
201.6
173,400
688,000
35.32
36.84
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 4
62.1 + 62.1 + 43.8 + 43.8
Inverter 3,600 at 60Hz
5.3 + 5.3 + 5.3 + 5.3
Direct On Line
FVC68D(PVE)
Stainless Steel Plate
45
30 + 30 + 22 + 22
192 + 192 + 116 + 116
10°C ~ 45°C(50°F ~ 114°F)
-5°C ~ 45°C(23°F ~ 114°F)
22.2(7/8)
44.5(1-3/4)
PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40
PT 40 + PT 40 + PT 40 + PT 40 PT 40 + PT 40 + PT 40 + PT 40
20
(755 × 997 × 500) x 4
(140 x 2) + (125 x 2)
(309 x 2) + (276 x 2)
59
63
73
77
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
380, 3, 60
tion rooms by ISO 3741 standard.
without prior notification.
under 10℃(50°F), and change the DIP switch on main PCB. (For more
information, refer a installation manual.)
Copyright © 2013 - 2019 LG Electronics Inc.
All rights reserved. Only training and service purposes.
[50Hz/60Hz]
66
ARWN660LAS4
ARWN200LAS4
ARWN200LAS4
ARWN140LAS4
ARWN120LAS4
184.8
159,000
630,600
207.9
178,800
709,500
36.70
38.26
Warm Gray , Mornig Gray
Hermetically Sealed Scroll
(Inverter) x 4
62.1 + 62.1 + 43.8 + 43.8
Inverter 3,600 at 60Hz
5.3 + 5.3 + 5.3 + 5.3
Direct On Line
FVC68D(PVE)
Stainless Steel Plate
45
30 + 30 + 29 + 22
192 + 192 + 135 + 116
10°C ~ 45°C(50°F ~ 115°F)
-5°C ~ 45°C(23°F ~ 115°F)
22.2(7/8)
53.98(2-1/8)
20
(755 × 997 × 500) x 4
(140 x 2) + (127 x 1) + (125 x 1)
(309 x 2) + (280 x 1) + (276 x 1)
61
63
75
77
1.0 ~1.5 x 2C
R410A
Electronic expansion valve
380-415, 3, 50
380, 3, 60

Advertisement