Samsung AC BNJDCH Series Installation Manual page 23

Hide thumbs Also See for AC BNJDCH Series:
Table of Contents

Advertisement

Setting the indoor unit addresses
Option No. for an indoor unit address: 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Before installing an indoor unit, be sure to set an address for the indoor unit by taking the following steps:
1 Make sure that the power is supplied to the indoor unit. If the indoor unit is not plugged in, it must include a power supply.
2 Set an address for each indoor unit using the remote control, according to your air conditioning system plan, by referring to the
following table and by following the steps in Common steps for setting the addresses and options on page 19.
• The indoor unit addresses (main and RMC addresses) are set to 0A0000-100000-200000-300000 by default.
• If indoor units and outdoor units match 1:1, you don't need to set the main address because it is automatically set by the outdoor
unit.
• If you are using on or off controller, set RMC address.
Option
SEG1
Function
Page
Indication
Details
Indication
and details
0
Option
SEG7
Function
Page
Indication
Details
Indication
and details
1
CAUTION
• The main address must be set to a value in the range 0 to 15. If you set other values, communication error will occur.
• If any of SEG5 and SEG6 is set to a value in the range A to F, the main address of the indoor unit does not change.
• If SEG3 is set to 0, the indoor unit maintains the existing main address even if SEG6 is set to a new value.
• If SEG9 is set 0, the indoor unit maintains the existing RMC address even if SEG11 and SET12 are set to new values.
SEG2
SEG3
Mode
Setting main address
Indication
Details
Indication
0
A
1
SEG8
SEG9
Setting RMC address
Indication
Reserved
0
1
SEG4
Indoor unit number
Details
Indication
No main
Reserved
address
0 to 1
Main address
setting mode
SEG10
Group channel (x16)
Details
Indication
No RMC
Reserved
address
RMC1
RMC address
setting mode
SEG5
SEG6
Indoor unit number
Details
Indication
Details
Tens
0 to 9
Units digit
digit
SEG11
SEG12
Group address
Details
Indication
Details
0 to 2
RMC2
0 to F
English
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac009bnjdchAc012bnjdchAc015bnjdchAc018bnjdch

Table of Contents