RenewAire EV130 Installation And Operation Manual

Energy recovery ventilator

Advertisement

I
NSTALLATION AND
M
E
NERGY
EV130 (door closed)
WARNING
R
F
, E
ISK OF
IRE
LECTRIC
OBSERVE ALL CODES AND THE FOLLOWING
1.
Before servicing or cleaning the unit, unplug the unit line
cord. Make sure unit is not running before opening its
door.
2.
This installation manual shows the suggested installation
method. Additional measures may be required by local
codes and standards.
3.
Installation work and electrical wiring must be done by
qualified professional(s) in accordance with all applicable
codes, standards and licensing requirements.
4.
Any structural alterations necessary for installation must
comply with all applicable building, health, and safety
code requirements.
5.
Connect this unit only to a 120VAC grounded receptacle
protected by a 15 or 20 amp circuit breaker. Do not
remove the unit's line cord.
6.
Do not install unit or controls where they can be reached
from a tub or shower.
7.
This unit must be properly ducted to the outdoors.
8.
Outside air inlet for this unit must be located away from
sources of hazardous air such as auto exhausts.
9.
Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment that might be installed in the area
affected by this equipment. If this unit is exhausting air
Due to continuing product development, specifications are subject to change without notice
EV130_200_300Man_Mar13.docx
EV130\EV200\EV300
ODEL
R
ECOVERY
S
,
I
.
HOCK
OR
NJURY
:
134777_012
4510 Helgesen Drive, Madison, WI, 53718
608.221.4499, 800.627.4499, Fax: 608.221.2824
support@renewaire.com www.renewaire.com
O
PERATION
V
ENTILATOR
EV130 (door open)
from a space in which chimney-vented fuel burning
equipment is located, take steps to assure that combustion
air supply is not affected. Follow the heating equipment
manufacturer's requirements and the combustion air
supply requirements of applicable codes and standards.
10. This unit is intended for general ventilating only. Do not
use to exhaust hazardous or explosive materials and
vapors. Do not connect this unit to range hoods, fume
hoods or collection systems for toxics.
11. When cutting or drilling into wall or ceiling, do not
damage electrical wiring and other hidden utilities.
12. Use the unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
CAUTION
1.
To avoid motor bearing damage and noisy and/or
unbalanced impellers, keep drywall spray, construction
dust, etc., out of the unit.
2.
Do not connect power to the units external control
terminals: this will damage the unit. The external
terminals are for use only with un-powered controls
designed for low-voltage operation.
Revised 03/2013
M
ANUAL
(ERV)
2013 RenewAire LLC
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EV130 and is the answer not in the manual?

Questions and answers

Summary of Contents for RenewAire EV130

  • Page 1 EV130\EV200\EV300 ODEL (ERV) NERGY ECOVERY ENTILATOR EV130 (door closed) EV130 (door open) from a space in which chimney-vented fuel burning WARNING equipment is located, take steps to assure that combustion air supply is not affected. Follow the heating equipment ISK OF...
  • Page 2: System Layout

    Do not install the exhaust outlet and fresh air inlet through the roof or roof soffit. If these are the only available Location of the Unit options call RenewAire technical support for help. Select a location so that: ♦ The preferred mounting location for the unit is on a concrete...
  • Page 3 When used for bathroom unit to the outside. Flexible insulated duct is typically used. exhaust, the EV130 should be used for no more than two See Table under “Duct Sizes”, below bathrooms, the EV200 for up to four bathrooms and the EV300 for up to six bathrooms.
  • Page 4: Installation

    Some local codes may require metal ducting all the way from the boots to the stale air grilles. Use rigid ducts to Due to continuing product development, specifications are subject to change without notice  Page 4 EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 2013 RenewAire LLC...
  • Page 5: Starting Up The Unit

    Care must be taken to insure that the duct is securely fastened and sealed to the duct collar. Optional controls: RenewAire offers a variety of controls specifically designed to Do not use more flex duct than necessary! work with the EV130/200/300 products. These include: PTL Flex duct is much more resistant to airflow than rigid duct;...
  • Page 6: Product Data

    Control: On-board 24 volt On-board 24 volt transformer 24 volt transformer and transformer and relay. and relay. relay. Due to continuing product development, specifications are subject to change without notice  Page 6 EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 2013 RenewAire LLC...
  • Page 7 Top View Right View EV200 Front View Top View Right View EV300 Front View Top View Right View Due to continuing product development, specifications are subject to change without notice  Page 7 EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 2013 RenewAire LLC...
  • Page 8 CERTIFIED RATINGS Due to continuing product development, specifications are subject to change without notice  Page 8 EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 2013 RenewAire LLC...
  • Page 9 Due to continuing product development, specifications are subject to change without notice  Page 9 EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 2013 RenewAire LLC...
  • Page 10 L. Terminal strip S. Divider cross bar Y. Literature packet F. Control board with standoffs M. Line cord with bushing T. Hardware kit Z. Filter Clip (EV130 only; sold singly; G. Blower assembly (complete) 2 per unit) EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013 ...
  • Page 11 U. Blower & wheel, motor side G. Blower assembly (complete) N. Filter (set of two) V. Duct collar (sold singly; 4 per unit) Due to continuing product development, specifications are subject to change without notice EV130_200_300Man_Mar13.docx 134777_012 Revised 03/2013  2013 RenewAire LLC Page 11...
  • Page 12: Use And Maintenance

    The primary contact for replacement The removal of dust and other small particles from your home filters for your RenewAire unit is the installing contractor. As is not the function of an ERV. an alternative, you may wish to produce your own filters.