Mitsubishi Electric MXZ-2C20NA2 Service Manual page 92

Outdoor unit
Hide thumbs Also See for MXZ-2C20NA2:
Table of Contents

Advertisement

3. 12-class unit in single operation (OUTDOOR UNIT: MXZ-2C20NA2 MXZ-2C20NA3 MXZ-2C20NA4)
(1) COOL operation
Data is based on the condition of indoor humidity
50%
Air flow speed: High
Inverter output frequency: 40 Hz
(PSIG)
170
160
150
140
130
120
65 70 75 80 85 90 95 100 105 110 115
Ambient temperature (˚F)
(2) HEAT operation
Data is based on the condition of indoor humidity
75%
Set air flow to High speed.
Inverter output frequency is 48 Hz.
OBH702N
<How to work fixed-frequency operation>
1. Set emergency switch to COOL or HEAT. The switch is located
on indoor unit.
2. Press emergency run ON/OFF button.
3. Compressor starts running at 40 Hz (COOL) or 48 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
6.0
86
5.0
4.0
80
3.0
75
2.0
70
1.0
40 Hz
0.0
(˚F)
65 70 75 80 85 90 95 100 105 110 115
7.0
6.0
5.0
4.0
3.0
2.0
15 20 25 30 35 40 45 50 55 60 65 70 75
92
40 Hz
Ambient temperature (˚F)
48 Hz
Ambient temperature (˚F)
86
80
75
70
(˚F)
75
70
65
(˚F)