BWI Eagle AIR-EAGLE XLT 441AN-6000-4-20O-120VAC Product Information Bulletin

900 mhz rf transceiver

Advertisement

Quick Links

AIR-EAGLE
900 MHz RF Transceiver
MODEL 441AN-6000-4-20O-120VAC
DESCRIPTION
The A
-E
XLT,
441AN-6000-4-20-120VAC
IR
AGLE
MODEL
transceiver capable of transmitting two 4-20mA or 0-5VDC inputs and
receiving two 4-20mA analog signals. Two transceivers are used
together to create a long-range radio frequency system that monitors
electrical apparatus from safe, convenient locations of up to 2500 feet
away. (Or longer with optional antennas) This unit is user-
programmable for up to eight network frequencies to allow multiple
systems to operate simultaneously in the same area without
interference.
INSTALLATION
Mount the A
-E
XLT TRANSCEIVER in a convenient location
IR
AGLE
1.
2.
Install wiring to input/output terminal strip.
Designate a "master" unit and set SEL1 Switch #3 accordingly.
3.
4.
Install antenna onto TNC connector on side of unit.
5.
Plug supplied AC wall plug adapter into 110VAC outlet.
TERMINAL STRIP WIRING
1
2
3
4
5
CONTROLS & INDICATORS
OUTPUT
Each Channel has a
FAULT LEDS
when the current output is open
105 Bonnie Drive
Butler, PA 16002
724-283-4681
724-283-5939 (fax)
www.bwieagle.com
®
XLT
s an RF
I
6
7
8
9
RED
LED that will turn on
PRODUCT INFORMATION
Dimensions (with mounting plate) 6.3" L x 4.8" W x 2.3" H
INPUT OPTIONS & FREQUENCY SET-UP
This transceiver is factory set for 4-20mA input, 4mA link loss and to
operate on frequency #1. If you wish to change the default settings, follow
the instructions using the table below:
1) Remove power from unit
10
2) Remove top cover.
3) Select desired input options and/or frequency using table below.
4) Reattach cover and apply power.
5) Programming is now complete.
SEL1
SWITCH
NUMBER
SW1
SW2
SW3
Note – A dedicated master unit MUST be selected.
SW4
SEL1
(SW5-7)
BULLETIN
Similar Model Pictured
INPUT CONFIGURATION
OPEN
4-20mA Input
(default)
Link Loss 4mA
(default)
Slave
(default)
Reserved for future use
FREQUENCY SET-UP
Network
SW5
Frequency
1
(default)
OPEN
OPEN
2
CLOSED
OPEN
3
OPEN
CLOSED
4
CLOSED
CLOSED
5
OPEN
OPEN
6
CLOSED
OPEN
7
OPEN
CLOSED
8
CLOSED
CLOSED
CLOSED
0-5VDC Input
Link Loss 20mA
Master
SW6
SW7
OPEN
OPEN
OPEN
OPEN
CLOSED
CLOSED
CLOSED
CLOSED

Advertisement

loading

Summary of Contents for BWI Eagle AIR-EAGLE XLT 441AN-6000-4-20O-120VAC

  • Page 1 105 Bonnie Drive PRODUCT INFORMATION Butler, PA 16002 724-283-4681 BULLETIN 724-283-5939 (fax) www.bwieagle.com ® AIR-EAGLE 900 MHz RF Transceiver MODEL 441AN-6000-4-20O-120VAC DESCRIPTION The A XLT, 441AN-6000-4-20-120VAC s an RF AGLE MODEL transceiver capable of transmitting two 4-20mA or 0-5VDC inputs and receiving two 4-20mA analog signals.
  • Page 2 Some jurisdictions do not allow the exclusion of implied warranties so this limitation may not apply to you. To obtain warranty service, contact BWI Eagle for a return SPECIFICATIONS material authorization. When returning equipment to BWI Eagle, the customer assumes the risk of damage or loss during shipping and is responsible for the shipping costs incurred.
  • Page 3 4-20mA Installation The above diagram shows a 4-20mA sensor hooked to channel 1 input. The 250 Ohm input resistor will drop a voltage of 1 Volt at 4mA and 5 Volts at 20mA. The sensor may be of any type and voltage that has a 4-20mA output.

This manual is also suitable for:

Air-eagle xlt 441an-6000-4-20-120vac