ABB CPS3200U Product Manual page 11

Remote power system 48 vdc input, +-190 vdc output converter/limiter system
Hide thumbs Also See for CPS3200U:
Table of Contents

Advertisement

Installation Category
CPS3200U output circuits are suitable for connection to telephone lines that are equipped with
primary lightning protectors consistent with UL 497. The user must provide protection on each
copper pair to a level corresponding to a CommScope 3C*EW Gas tube primary protector or
equivalent gas tube protector [For example: 3C3EW provides the part in a red color]. This protector
has a voltage breakdown range of 265-465 Volts and an impulse spark over range of <265-700 Volts.
The 5-Pin protector must be marked as a "special circuit" consistent with the marking protocol in the
users network. Protectors are provided by the telco customer.
Network equipment and components along the powering circuit shall have suitable insulation
resistance at 200 Vdc from each conductor to ground and a total insulation resistance suitable for
400 Vdc from line to line.
Page 11
© 2021 ABB. All rights reserved.