A steam trap for steam-using equipment, enabling equipment efficiency to be optimized while conserving energy
through rapid drain discharge
60Y
Working pressures and back pressures
Trap Series 60Y and 60R are designed to
operate at maximum working pressure of
4 MPa, but they have been set to function
at maximum efficiency at pressures from
0.14 MPa to 3 MPa. When they operate in the
specified pressure range, the best results
will be obtained after carrying out the special
adjustments listed as follows:
1. When operating at pressures up to
0.14 MPa, loosen lock nut and turn control
cylinder stem 1½ to downwards.
2. When operating in the pressure range
3 MPa ~ 4 MPa, loosen lock nut and turn
control cylinder stem ¾ to upwards.
3. The traps have been preset to operate
back pressures of up to 40% of trap inlet
pressure. By turning the control cylinder
stem 1½ to downwards, they can operate
against back pressures up to 72%.
Emerson.com/FinalControl
CAUTION
When following the above procedure, be sure
to make the adjustments after loosening the
lock nut. Use a screw driver to hold the control
cylinder stem in place. When tightening the lock
nut after completing the ad-justments, verify that
60R
the stem is set firmly in position, since it may turn
together with the lock nut. Except when making
the above adjustments, be sure not to touch the
stem and lock nut.
Operating characteristics
Trap Series 60Y and 60R are extremely sensitive
to the generation of condensate, discharging
high-temperature condensate a little at a time.
When a big volume of condensate accumulates,
as for instance during starting, the trap
discharges continuously. With little volume, it
discharges intermittently.
© 2020 Emerson. All Rights Reserved.
VCIOM-15468-EN 20/06

Advertisement

loading

Summary of Contents for Emerson YARWAY 60Y Series

  • Page 1 3. The traps have been preset to operate back pressures of up to 40% of trap inlet pressure. By turning the control cylinder stem 1½ to downwards, they can operate against back pressures up to 72%. Emerson.com/FinalControl VCIOM-15468-EN 20/06 © 2020 Emerson. All Rights Reserved.
  • Page 2: Section 1 - Installation

    YARWAY IMPULSE STEAM TRAPS, SERIES 60Y AND 60R INSTALLATION, OPERATION AND MAINTENANCE MANUAL RATINGS TABLE Max. working pressure Max. working temperature Series (MPa) (°C) Strainer Built-in Built-in Built-in SECTION 1 - INSTALLATION SECTION 2 - PIPING ARRANGEMENT 1. Before installing trap, blow out piping 1.
  • Page 3: Section 3 - Inspection And Maintenance

    YARWAY IMPULSE STEAM TRAPS, SERIES 60Y AND 60R INSTALLATION, OPERATION AND MAINTENANCE MANUAL SECTION 3 - INSPECTION AND MAINTENANCE 4. The outer diameter of the valve disc is larger than the bore of the control cylinder’s open 1. To prolong trap life and assure proper end.
  • Page 4: Parts List

    YARWAY IMPULSE STEAM TRAPS, SERIES 60Y AND 60R INSTALLATION, OPERATION AND MAINTENANCE MANUAL PARTS LIST FIGURE 2 - SERIES 60Y Item Body Valve seat Seat gasket Valve piece Control cylinder Bonnet Cap nut Lock nut Cap gasket Screen Screen cap Gasket Flow Plug...
  • Page 5: Size Table

    YARWAY IMPULSE STEAM TRAPS, SERIES 60Y AND 60R INSTALLATION, OPERATION AND MAINTENANCE MANUAL SIZE TABLE Parts name Figure No. HEX (mm) Torque (N·m) Bonnet Bonnet Seat 15, 20, 25 32, 40, 50 Screen SECTION 5 - REPAIR PARTS SECTION 6 - SPARE PARTS The Repair Kits of Trap Series 60Y and 60R are For one year service, it is recommended to Supplied as a set consisting of six items: valve...
  • Page 6 VCIOM-15468 © 2020 Emerson Electric Co. All rights reserved 06/20. Yarway is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners.

This manual is also suitable for:

Yarway 60r series