Regulator installation

3.

3.1. Regulator location

The regulator is designed for wall installation in the interior environment of buildings. For proper
-
functioning, the regulator must be located at the reference point – in the residence zone about 1.5 m
above the floor; it must not be close to the door or window openings in the area where is a natural air
movement (draft), direct sun light or any sources radiant heat.
The maximum recommended distance of the regulator from the regulated EC-motor is 100 m at the
-
conductor cross-section of 1 mm2.
Ambient working temperature 0 to 40°C, humidity 0-90% non-condensing.
-

3.2. Installation

The regulator can be mounted on a wall:
-
In an under-plaster electrical junction box (hereinafter referred to as the boxes) with the central
o
opening for the supply cable. The supply cable must be prepared in the wall. Connect the cable
according to the relevant wiring diagram. Complete the assembly with mounting the front cover
- by snapping in.
o In an under-plaster electrical junction box (hereinafter referred to as the boxes) with the side
opening for the supply cable. The supply cable is routed along the wall surface, e.g. on a wiring
bar. Attach the regulator to the box with self-tapping screws with a half-round head 3 x 13 mm
(not included in the delivery) into the prepared holes in the box.Connect the cable according to
the relevant wiring diagram. Complete the assembly with mounting the front cover - by snapping
in.
Verze 1 – GBR (11.3.2020)
4
D-502-0168