Page 1
INSTRUCTIONS FOR OPERATION AND INSTALLATION OF THE EXTRACTION UNIT AND THE ATACAMA DESTRATIFICATION UNIT Verze 1 – GBR (11.3.2020) D-502-0165...
CONTENT General information ............................... 4 1.1. Introduction .................................. 4 1.2. Use of the unit ................................4 1.3. Transport, inspection of delivery and storage ......................4 1.4. Contents of the package .............................. 5 1.5. Before start of installation ............................5 Technical parameters ..............................5 2.1.
Page 3
Regulation ..................................15 4.1. General Information –Safety ............................. 15 4.2. Control elements ................................ 15 Atacama heating unit wiring diagram ......................... 16 5.1. Wiring diagram for connection of units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 ..16 5.2. Connection of chained units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 ...
1. General information 1.1. Introduction This document "Installation and Operating Manual" is intended for the heating unit Atacama (hereinafter referred to as the "Unit") used to heat the required space by warm air. Detailed familiarisation with this document is important for correct and safe installation and functioning of the unit. Failure to follow the conditions in this document may result in malfunction of the unit.
1.4. Contents of the package Atacama heating unit Assembly console Assembly accessories – screw M6x20 Quick manual + Safety Data Sheet Name plate 1.5. Before start of installation Before starting the installation, we recommend that you attach the serial nameplate (normally delivered with the unit in its package) to the operational documentation (e.g.: equipment operating book, etc.), which is subsequently kept for a later maintenance record and the respective servicing.
2.2. Main dimensions and minimum working space requirements for Atacama units ATACAMA HEATING UNIT MIN. INSTALLATION AND OPERATING SPACE ATACAMA-D DESTRATIFICATION UNIT MIN. INSTALLATION AND OPERATING SPACE Verze 1 – GBR (11.3.2020) D-502-0165...
2.3. Technical data EC Declaration of Conformity – the current and full version of the EC Declaration of Conformity can be seen on our website www.xvent.cz under the Atacama product documents 2.4. Technical data of water heaters Verze 1 – GBR (11.3.2020)
3. Installation of heating units in the working position 3.1. General information, recommendations and safety during installation of the Atacama heating unit 3.1.1. Electrical safety before assembling the unit Before starting any assembly works, it is necessary to switch off the power supply to the prepared electrical installation for subsequent activation of the unit.
3.5. Water exchanger connection 3.5.1. Connection of the unit to the existing hot water distribution system Connect the unit to the heating system using a flexible connection (e.g. flexible hoses – with braided armour). The heating system piping must not put any load on the exchanger throats. 3.5.2.
3.5.3. Venting (discharge) valve Water supply and drainage necks are marked on the water exchanger collectors. To tighten the connected piping to the unit, use the hexagonal profile on the water exchanger neck. This prevents the exchanger outlet from being overturned, which may result in irreversible damage to the water exchanger. Drain the heating medium from the exchanger, by loosening the lower vent screw.
The supply voltage of the unit must be connected in such a way that all poles of the network are disconnected from the power supply by one element (e.g. main switch). The unit inlet phase must be connected via a protective power circuit breaker (protective switch) according to the corresponding current.
3.6.4. Connection to the mains Connection to the mains is recommended by means of the wiring box with the corresponding electrical protection class (according to the installation space). The electric installation box must be attached to a solid non-combustible surface at the maximum distance from the unit according to length of the motor cables.
3.7. Direction lamellas setting Adjust the exhaust lamellas by deflecting them from the front exhaust cover. The minimum lamellas deflection for a correct function of the unit is from 45°, which allows ideal direction of the blown air into the heated space. The lamellas must always be opened during operation of the unit Gradually flex the lamellas from top to bottom 4.
5. Atacama heating unit wiring diagram 5.1. Wiring diagram for connection of units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 5.2. Connection of chained units ATA1-2-ECV, ATA1-3-ECV, ATA4-ECV with regulator ELEMENTAIR-E-M1 Verze 1 – GBR (11.3.2020) D-502-0165...
5.3. Connection of units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1 5.4. Connection of chained units ATA1-2-ECS, ATA1-3-ECS, ATA4-ECS with regulator ELEMENTAIR-B-M1 Verze 1 – GBR (11.3.2020) D-502-0165...
5.5. Connection of units withoutregulation Unit – the fan operation – can be switched on and off only by the ON/OFF controls at the power supply to the fan. Switching/disconnection of the supply voltage can be solved by e.g.: timer, spatial thermostat. Other regulation elements will not be connected to the regulator functionality.
If the temperature in the space is assumed to fall below 5°C and the temperature of the heating water is low, there is a risk of the heat exchanger freezing – bursting. Unit – exchanger is not equipped with anti- freeze protection.
8. Service Comply with the general country-specific provisions. In case of any service activity, it is necessary to disconnect the unit from the mains and switch off the heating water supply to the unit heat exchanger. Work must be carried out only after the exchanger has cooled down. Any electrical service work must be carried out by a person with professional qualifications.
Party. 11. Conclusion If you have any doubts about this product, please do not hesitate to contact us. Contact address: Xvent s.r.o. Poděbradská 289 53009 Pardubice-Trnová Czech Republic www.xvent.cz Verze 1 – GBR (11.3.2020) D-502-0165...