Quick Start Guide
the proper power supply, conduit, and other accessories necessary to
comply with these standards.
The transmitter requires external power. Ensure access to a suitable power
source.
Table 3-2: Electrical Data
Electrical data
Power input
Pulsed circuit
4-20mA output circuit
Um
Coil excitation output
Environmental considerations
Remote mounted transmitters may be installed in the control room to
protect the electronics from the harsh environment and to provide easy
access for configuration or service.
Table 3-3: Transmitter housing environmental ratings
Type
Ingress protection
NEMA
Pollution Degree
Maximum altitude rating
Note
For complete environmental and other specifications, refer to the product
reference manual.
8
AC power:
90–250 VAC (
Standard DC power:
12–42 VDC (
Internally powered (Active): Outputs up
to 12 VDC, 12.1 mA, 73 mW
Externally powered (Passive): Input up to
28 VDC, 100 mA, 1 W
Internally Powered (Active): Outputs up
to 25 mA, 24 VDC, 600 mW
Externally Powered (Passive): Input up to
25 mA, 30 VDC, 750 mW
250 V
2.0 A, 85 V max, 80 W max
Rating
IP66, IP69
4X
2
13,123 ft (4000 m) at rated input
power voltage (90–250 VAC)
16,404 ft (5000 m) at maximum
input power voltage of 150 VAC
Rosemount
8782 Slurry Magnetic Flow Meter Transmitter