No SELV/PELV power circuits may be connected to the connecting
terminals of the relay outputs.
Exceeding this capacity could lead to the destruction of the device,
fires or electric shocks.
The circuit to which the device and the load will be connected must
be protected by a circuit breaker in accordance with EN60898-1
(tripping characteristic B or C, max. 16 A rated current, min. 6 kA
breaking capacity, energy limitation class 3). Installation regulations
according to VDE 0100 and HD382 or 60364 must be observed. The
circuit breaker must be easily accessible to the user and marked as
the disconnecting device for the actuator.
Before the actuator is connected, remove the fuse from the fuse
box.
Except for configuration, the device may only be operated with an
associated switch cover.
The device has not been designed to support safety disconnection.
Devices with electronic power supply units (e.g. TV or high voltage
LED light sources) are no ohmic loads. They can generate inrush
currents of more than 100 A. Switching such kind of loads may lead
to premature wear of the actuator. In such cases, we recommend
using inrush current limiters at the switching outputs.
If you use the device in a security application it has to be operated in
connection with an UPS (uninterruptible power supply) in order to
bridge possible power failure.
The device must only be operated within residential buildings.
Using the device for any purpose other than that described in this