EFC 3600
2.3.2 Analog Input Terminals (+10 V, Vr1, GND, +I)
Fig. 2-5: Analog input terminals (+10 V, Vr1, GND,+I)
For connections of low level analog signals, which are easily affec-
●
ted by external interference, the wiring length should be as short
as possible (less than 20 m). Shielded cables must be used.
Incorrect operation may occur due to interference on the analog
●
signal. In such cases, connect a capacitor and ferrite core at the
output side of the analog signal, as shown above.
DOK-RCON03-EFC-3600***-IN02-EN-P
Bosch Rexroth AG
Electric Installation
11/35