AVK 145 Series Installation, Operation And Maintenance Manual

AVK 145 Series Installation, Operation And Maintenance Manual

Gate valves for water and fire protection

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 145 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for AVK 145 Series

  • Page 1: Table Of Contents

    7.2.1 Handwheel replacement 7.2.2 Stem seal O-ring replacement 7.2.3 Supervisory switch installation 8. Troubleshooting guide 9. Parts and service COPYRIGHT©AVK GROUP A/S 2020 - AVK INTERNATIONAL A/S, BIZONVEJ 1, DK-8464 GALTEN - WWW.AVKVALVES.EU MI GateValve 145 rev. AC 2020 GB...
  • Page 2: Introduction

    1. INTRODUCTION AVK series 145 resilient wedge gate valves for use in fire protection are UL/FM approved and designed to be maintenance free. They have a rated working pressure of 250 PSI and are available in DN65-200. All series 145 valves are configured for CTC operation and have flanged end connections to ANSI B16.42 class 150.
  • Page 3: Parts List

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 3. PARTS LIST Item Description Material F201 Upper stem nut Copper alloy F202 OS&Y handwheel Ductile iron, ASTM A536 F203 Anti friction washer...
  • Page 4: Inspection After Unloading

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 INSTALLATION AND TESTING 4.2 INSPECTION AFTER UNLOADING At the time of receipt, the resilient seated gate valves should be inspected for damage in shipment. The initial inspection should...
  • Page 5: Application Hazards

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 After installation, the newly installed piping sections, including valves, should be tested at some pressure above the system designed pressure. The test pressure should not exceed the rated working pressure of the valve. After the test, any trapped pressure in the body of the valve should be relieved.
  • Page 6: Operation

    AVK series 145 NRS (Non-Rising Stem) valves - Turns to open Valve size Turns to open DN65 DN80 DN100 DN150 DN200 AVK series 145 OS&Y (Outside Stem and Yoke) valves - Turns to open Valve size Turns to open DN65 DN80 DN100 DN150 DN200 6.3 MAINTENANCE PROCEDURES...
  • Page 7: Repair Procedures

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 REPAIR PROCEDURES 7. REPAIR PROCEDURES In most instances, in order to keep system down time to a minimum, complete valve assembly replacement is implemented.
  • Page 8: Upper Stem Seal Components Repair

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 NRS (Non-Rising Stem) VALVE REPAIRS: NRS (Non-Rising Stem) VALVE REPAIRS: 7.1.2 UPPER STEM SEAL COMPONENT REPAIR F220 F220 F221 UPPER STEM SEAL COMPONENT REPAIR:...
  • Page 9: Bonnet Gasket Replacement

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 NRS (Non-Rising Stem) VALVE REPAIRS: NRS (Non-Rising Stem) VALVE REPAIRS: 7.1.3 BONNET GASKET REPLACEMENT BONNET GASKET REPLACEMENT WARNING BONNET GASKET REPLACEMENT To perform the following steps, make sure that the water...
  • Page 10: Os&Y Valve Repairs

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 OS&Y (Outside Stem & Yoke) VALVE REPAIRS: OS&Y (Outside Stem & Yoke) VALVE REPAIRS: F201 7.2 OS&Y VALVE REPAIRS F201 F202 HANDWHEEL REPLACEMENT (Figs.6A,6B) 7.2.1 HANDWHEEL REPLACEMENT (Fig.
  • Page 11: Stem Seal O-Ring Replacement

    INSTALLATION, OPERATION AND MAINTENANCE MANUAL – ORIGINAL VERSION AVK GATE VALVES FOR WATER AND FIRE PROTECTION SERIES 145 OS&Y (Outside Stem & Yoke) VALVE REPAIRS: OS&Y (Outside Stem & Yoke) VALVE REPAIRS: 7.2.2 STEM SEAL O-RING REPLACEMENT (Fig. 6A and...
  • Page 12: Supervisory Switch Installation

    Relieve pressure and bleed off any air build-up. 9. PARTS AND SERVICE For information on parts and service for your area, please contact AVK International A/S. Make a note of the valve model number and size which is to be found on the valve and contact:...

Table of Contents