• Interior Delay: This interior zone follows Entry Delay Time #1 (Address 010) during normal arming. When arming using the "No Entry"
button, this zone becomes an interior instant.
• Perimeter Homeguard: This zone type is active when the panel is armed. When the panel is armed perimeter only, this acts like an
Entry/Exit Delay #1. When armed full, this is an instant zone.
• Perimeter Follower Homeguard: These zones act like an Entry/Exit Delay #1 zone when the panel is armed in the perimeter only
mode. When the panel is fully armed, these zones are ignored during the entry/exit delay time if this zone or an instant zone is violated
first.

9.26 Address 034, 035, 036, 037 - Zone Action

0 = Alarm on Short, Alarm on Open (Default)
1 = Alarm on Short, Trouble on Open
2 = Alarm on Open, Trouble on Short

9.27 Address 038, 039, 040, 041 - Output Type

For Intrusion and Fire Zones only:
0 = Invisible (not valid for Fire Zones)
1 = Silent (not valid for Fire Zones)
2 = Steady Alarm Output (Default)
3 = Pulsing Alarm Output
• Invisible: This is a zone programmed not to have an alarm output or an alarm display at any keypad when activated. An alarm signal
will be sent, but the keypad display will not indicate an alarm while this zone is violated. Invisible alarm zones are recommended for
holdup alarms.
• Silent: This is a zone programmed to activate the visual display at the kaypad, but not audible signals. If this zone is also an entry zone,
an entry tone will sound when this zone is activated.
• Steady: When this zone alarms the Alarm Output will come on steady, unless it is already pulsing, in which case it will remain pulsing.
• Pulsing: The pattern for the pulsing audible output is determined by the Fire Alarm Cadence as set in Address 009. When zones are
tripped which could cause both pulsing and steady outputs, the pulsing output will prevail. The alarm outputs will continue to be
activated until the bell cutoff timer times out or is reset, then they will silence.
• Keyswitch does not allow Force Arming: The system will not arm if any zones are in the "Not Ready" condition.
• Keyswitch allows Force Arming: The system will be allowed to arm by automatically bypassing "Not Ready" zones. The Force Arming
only works on zones that are set as Bypassable in Address 042-045. The "Force Arm Limit", set in Address 002, will be ignored when
arming with keyswitches.
Page 34
P/N 39818D
For Keyswitch Zones Only:
0 = Keyswitch does not allow Force Arming
1 = Keyswitch allows Force Arming