Current
Table 20 Current boundary limits slave BMS
Name
Charging over current warning
Discharging over current warning
Balancing
Table 21 Balancing boundary limits slave BMS
Name
Offset cell voltage
Balancing cell voltage
Battery pack current
Deviation voltages and temperatures
Table 22 Deviation voltage and temperature boundary limits slave BMS
Name
Deviation cell voltage
Deviation cell temperature
Boundary condition
Level
Economic
Set
> 0.6C
Clear
<= 0.6C
Set
> 1.0C
Clear
<= 1.0C
Boundary condition
Level
Economic
current within ±5% battery
capacity
Boundary condition
Level
Economic
Difference highest and lowest cell
Set
voltage >= 300 mV;
lowest cell voltage >= 3325;
current within ±5% battery capacity
Difference highest and lowest cell
Clear
voltage < 240 mV;
lowest cell voltage >= 3325;
current within ±5% battery capacity
Set
Difference highest and lowest cell
temperature >= 15 °C
Clear
Difference highest and lowest cell
temperature < 12 °C
64
Innovation in energy storage
Version 2.3 – 21-9-2022
Performance
Time
> 1C
10 sec.
<= 1C
10 sec.
> 1.5C
10 sec.
<= 1.5C
10 sec.
Performance
Time
> 5 mV
5 min.
>= 3805 mV
5 min.
5 min.
Performance
Time
4-6 min.
4-6 min.
4-6 min.
4-6 min.