Lennox Harmony II Zone Control System Installation Instructions Manual page 41

Table of Contents

Advertisement

Option 3 − Troubleshooting Harmony
This troubleshooting diagram lists common trouble spots. Rather than providing solutions, this diagram asks questions about the hookup and
operation of system equipment. Good troubleshooting skills combined with information provided elsewhere in this manual are necessary.
S Is outdoor (balance point) thermostat
installed?
S Does systems use compressor heat
to satisfy primary heating demand
when above balance point?
S Does system use gas heat to satisfy
primary heating demand when below
balance point?
Outdoor
Thermostat
S Are appropriate inputs
being received?
DTR Kit (optional)
SLC Kit (optional)
S Refer to FM21 input/
output tables in FM21
installation instruc-
tions.
®
II Zone Control with FM21 (Cont'd)
S Is discharge probe (DT1) installed?
S Probe should be located between coil and fur-
nace. Is probe in correct location?
S Is it wired correctly?
S During defrost operation, does furnace cycle tem-
per discharge air?
FM21 Heat Pump Control
S Are jumpers correctly
installed?
S Refer to FM21 instal-
lation manual.
Indoor Unit
Outdoor Unit
S Does outdoor unit respond to demand?
S Is it operating properly?
S Test defrost. Does outdoor unit initiate and terminate
defrost correctly?
S Is W1 energized during defrost?
S Does FM21 respond appropriately during defrost?
S Does Harmony control center respond appropriately
during defrost?
Figure 32
Page 41
S 24VAC from furnace trans-
former or 75VA transform-
er (DTR1 Option) to R"?
S Does furnace respond to
ouputs? Cooling? Heat-
ing? Defrost? Em. Heat?
S Does blower speed
change as zone demand
changes? If no, does DS
output vary from 0 to
25VDC?