BSR-1000/MAR, BSR-1001/MAR BSR-1002/MAR, BSR-1004/MAR Analogue Addressable Fire Alarm Panel 1, 2 and 4 loops Installation Programming Operation WARNING!!! READ THIS MANUAL PRIOR TO ANY INSTALLATION OR USE...
Date 29/6/2021 Document number 921100409_09_002 Page 2 of 73 Index 1 General Information ---------------------------------------------------------------------------------------------------------------------- 5 General description -------------------------------------------------------------------------------------------------- 5 Safety ------------------------------------------------------------------------------------------------------------------- 5 Indicators and Controls --------------------------------------------------------------------------------------------- 6 1.3.1 Control panel’s front ------------------------------------------------------------------------------------------- 6 1.3.2 Control panel’s keypad ---------------------------------------------------------------------------------------- 7 1.3.3 LED indicators --------------------------------------------------------------------------------------------------- 8 2 Functions 10 Control panel operating states ----------------------------------------------------------------------------------- 10...
Page 3
Date 29/6/2021 Document number 921100409_09_002 Page 3 of 73 4.4.2 Connecting conventional sirens ---------------------------------------------------------------------------- 39 Panel network connections --------------------------------------------------------------------------------------- 40 General connections diagram ------------------------------------------------------------------------------------ 41 Other connections -------------------------------------------------------------------------------------------------- 42 5 Technician Menu ------------------------------------------------------------------------------------------------------------------------- 44 Test Menu ------------------------------------------------------------------------------------------------------------ 46 5.1.1 Walk test --------------------------------------------------------------------------------------------------------- 46 5.1.2 All zones in test ------------------------------------------------------------------------------------------------ 46 5.1.3...
Page 4
Date 29/6/2021 Document number 921100409_09_002 Page 4 of 73 7 BSR-100X PC software application ------------------------------------------------------------------------------------------------- 64 Programming the panel -------------------------------------------------------------------------------------------- 64 Loop calculation ----------------------------------------------------------------------------------------------------- 67 Battery Calculation-------------------------------------------------------------------------------------------------- 68 8 BSR-1000/MAR Repeater panel ------------------------------------------------------------------------------------------------------ 68 General ---------------------------------------------------------------------------------------------------------------- 68 Functions-------------------------------------------------------------------------------------------------------------- 69 Installation ------------------------------------------------------------------------------------------------------------ 69 Wiring ------------------------------------------------------------------------------------------------------------------ 69 Setup repeater network -------------------------------------------------------------------------------------------- 69 8.5.1...
5 of 73 1 General Information Thank you for your trust in our products Olympia Electronics – European manufacturer 1.1 General description The BSR-100X/MAR series of Analogue Addressable Fire Alarm Panels consists of 3 models (1, 2 and 4 loop connections), named BSR-1001/MAR, BSR-1002/MAR and BSR-1004/MAR respectively, all sharing the same control interface, functionality and indications.
Date 29/6/2021 Document number 921100409_09_002 Page 6 of 73 1.3 Indicators and Controls The control panel’s LCD screen displays information regarding the current state of the fire detection system. The front face is also equipped with LED indicators for essential indications (alarm, fault, status, zones, etc.).
Date 29/6/2021 Document number 921100409_09_002 Page 7 of 73 1.3.2 Control panel’s keypad Resets the panel from alarm state to RESET quiescent, clears current faults SIREN Stops or resumes sirens during SILENCE / alarm mode RESOUND Evacuation of the building. Manual EVACUATE activation of all alarm outputs BUZZER...
Date 29/6/2021 Document number 921100409_09_002 Page 8 of 73 1.3.3 LED indicators The LED indicators are divided into groups, according to their purpose. Their color also define their event type, red LEDs indicate alarm, yellow LEDs indicate status or fault, green LED indicates the mains power. In details, LEDs from top to bottom are: System is in fire GENERAL ALARM...
Page 9
Date 29/6/2021 Document number 921100409_09_002 Page 9 of 73 On the figure below appear the LED indicators below the screen. All of them refer to specific faults of the control panel (according to the description) and are yellow. GENERAL FAULT General panel fault System fault SYSTEM FAULT...
Date 29/6/2021 Document number 921100409_09_002 Page 10 of 73 2 Functions 2.1 Control panel operating states The operating states of the control panel are the following: Α) Quiescent Β) Prealarm C) Alarm D) Fault 2.2 Quiescent state The state where there are not any current alarms, prealarms or fault events is called quiescent state. The message “SYSTEM READY”...
Date 29/6/2021 Document number 921100409_09_002 Page 11 of 73 Figure 2-2.Prealarm on main screen 2.4 Alarm state If a detection device triggers a fire alarm signal, the red "GENERAL ALARM" indicator is being lit. On the first row the message “X – ALARMS” is shown, where X represents the number of the current alarms. Figure 2-3.Alarm on main screen The second and the third row, describe the first and the last alarm event respectively.
Date 29/6/2021 Document number 921100409_09_002 Page 12 of 73 Access Level Functions 1 (Access Level 1) This level refers to the functions that a simple user can do directly via the keypad while on main screen. No code (password) is required for these functions “BUZZER SILENCE”: On the event of a fault, or an alarm, if this key is pressed, the built-in buzzer stops sounding.
Date 29/6/2021 Document number 921100409_09_002 Page 13 of 73 More information regarding the options in the main menu: VIEW DISABLEMENT: View all disabled segments of the fire detection system. USER MENU: This menu includes a set of settings only accessible by user with access level “2”. ...
Date 29/6/2021 Document number 921100409_09_002 Page 14 of 73 2.7.3 Information By selecting “INFORMATION” the menu displays the available options on the first screen below. There are additional options following that will appear by scrolling down the menu with down key, as shown in the following screens.
Page 15
Date 29/6/2021 Document number 921100409_09_002 Page 15 of 73 The “ZONES IN ALARM” option will display all zones that are in alarm state. If no zone is in alarm, the screen on the right will be displayed. The “ZONES IN FAULT” option will display the zones that are in fault. If no zones are in fault the screen on the right will be displayed.
Page 16
Date 29/6/2021 Document number 921100409_09_002 Page 16 of 73 By selecting “LOOPS” option, the screen on the right appears. The first line, “STATUS”, shows if the loop is present and active. The rest of the lines, indicate how many of each point type are registered into this loop.
Page 17
Figure2-24.Ethernet adaptor By selecting “TECHNICIAN INFO” option, the screen on the right appears. The OLYMPIA ELECTRONICS S.A. contact info is displayed by default. This information can be changed via PC software or web interface by the installer, in order to provide the desired company’s name and telephone number.
Page 18
Date 29/6/2021 Document number 921100409_09_002 Page 18 of 73 By selecting “PANEL SOFT VERSION” option, the screen on the right appears, displaying the firmware installed on the panel, for the CPU and the loop circuits. The last line also displays the panel’s serial number. Note! On the screen it is only displayed the firmware for the installed loops.
Date 29/6/2021 Document number 921100409_09_002 Page 19 of 73 3 User’s Menu This chapter contains information for user access with access level 2 (code protected). Press Enter key once to enter main menu. User menu option appears on the monitor (figure 4-1). Figure3-1.Main Menu Then select “USER MENU”...
Page 20
Date 29/6/2021 Document number 921100409_09_002 Page 20 of 73 Figure 3-3.User’s menu diagram In this menu, the following basic functions can be done RESET the system (clears current alarms, prealarms and faults) SIREN SILENCE in case of an alarm event, to mute audible alarm. ...
Date 29/6/2021 Document number 921100409_09_002 Page 21 of 73 3.1 Enable / Disable segments Via the "ENABLE" and “DISABLE” options, the user can enable or disable any segment of the control panel, as shown in figures 3-4. By disabling a segment, all faults and alarm signals received by that segment will be ignored by the control panel.
Date 29/6/2021 Document number 921100409_09_002 Page 22 of 73 3.2 Delays Menu Via “DELAYS” option the user can activate or deactivate time delays in general. If a delay has been applied to at least one segment of the control panel, then DELAYS ON indicator will light yellow. By activating the delays, this setting will be applied permanently.
Date 29/6/2021 Document number 921100409_09_002 Page 23 of 73 Figure3-11.Change time By selecting “WORKING DAYS” the screen on the right is shown. Use up/down keys to select day and click right key to enable or disable this day. Filled box equals to enable. When set press Enter to save.
Date 29/6/2021 Document number 921100409_09_002 Page 24 of 73 3.6 PC Communication The “PC COMMUNICATION” option is used to download panel’s data to a PC via USB cable, running the BSR-100X software application. This function may seem useful, in order to keep event logs, keep a record of current configuration as a backup or to gather and send useful data to manufacturer in terms of troubleshooting.
Date 29/6/2021 Document number 921100409_09_002 Page 25 of 73 3.7 Operating via PC (Ethernet) This chapter contains information on how to monitor and configure the panel remotely via a common web browser (web interface), on a Local Area Network (Ethernet connection required). 3.7.1 Control panel web interface To operate the panel via PC (web interface) no special software is required.
Date 29/6/2021 Document number 921100409_09_002 Page 26 of 73 3.7.3 View disablement If there are any disabled segments on the system, by clicking on this link, all disabled segments will be displayed in separate lines. 3.7.4 Information The “INFORMATION” link will lead to a submenu with multiple available informational options. These options are described below: 3.7.4.1 Information Panel This option will display the page below, with the most significant data of the control panel (hardware...
Page 27
Date 29/6/2021 Document number 921100409_09_002 Page 27 of 73 3.7.4.4 Information Loops This option will display loop information, regarding the connected point types to each one of them. 3.7.4.5 Information Points This option will open the page below. On the input boxes you can enter the point’s loop and address. By clicking “OK”...
Page 28
Date 29/6/2021 Document number 921100409_09_002 Page 28 of 73 3.7.4.7 Information Extra Relays Same as panel relays, the extra relays option contains similar information for the extra relays settings. Extra relays belong to peripheral equipment and are not pre-installed in the control panel. 3.7.4.8 Information Conventional Sirens This page displays all settings for the conventional sirens.
Date 29/6/2021 Document number 921100409_09_002 Page 29 of 73 3.7.5 All events All panel’s events are appearing in chronological order. Due to the high capacity of recorded events (7k), the events are divided into pages. 3.7.6 User’s menu By selecting “USER MENU” the systems asks for user code (access level 2): Enter the user’s code and click “SEND”.
USB connection with the use of the PC software application BSR-100X. The program is free of charge and can be downloaded from the official site of Olympia Electronics S.A. https://www.olympia-electronics.com/en/support/software All the following connections must be made while the control panel is deactivated, disconnected from mains power supply and batteries.
Date 29/6/2021 Document number 921100409_09_002 Page 31 of 73 4.3 Control panel installation The control panel installation must be done by trained personnel exclusively. Do not touch, add or remove boards or components, perform connections or do other modifications, while mains power supply is connected.
Date 29/6/2021 Document number 921100409_09_002 Page 32 of 73 Figure4-2.Panel mountings and holes The panel must be placed at least 1m above floor level and 1m bellow roof level and at the minimum distance of 30cm from other devices. No other supply lines should cross the wall behind the panel except the panels own power supply.
Date 29/6/2021 Document number 921100409_09_002 Page 33 of 73 Figure 4-3.Mains power supply connection Caution! 1. Any assignment of installation, repairs or electrical equipment maintenance must be executed with both mains power supply and batteries disconnected. 2. Connect the batteries and enable mains power supply to the control panel only after all other cable connections have been completed.
Page 34
Date 29/6/2021 Document number 921100409_09_002 Page 34 of 73 The batteries must be connected in series. In the battery area there are two wires, one red and one black for connecting the batteries. The red wire must be connected to the positive pole of the first battery; the black wire must be connected to the negative pole of the second battery.
Date 29/6/2021 Document number 921100409_09_002 Page 35 of 73 4.4 Wiring For compliance with the electromagnetic compatibility (EMC) requirements, the connections of the peripheral devices to the panel must be done with shielded cables. Every cable’s shield must be connected to the vessel hull (“Protective Earth”), to achieve the minimum electrical distance possible.
Date 29/6/2021 Document number 921100409_09_002 Page 36 of 73 4.4.1 Loop Connections All models of the BSR-100X/MAR family, BSR-1001/MAR, BSR-1002/MAR and BSR-1004/MAR share the same architecture, thus same loop connection method. They differ only on the available loop connection outputs (1, 2 or 4). The output connections, maximum consumption and the connection diagrams that are going to be mentioned in the next paragraphs are common to all panels.
Page 37
Date 29/6/2021 Document number 921100409_09_002 Page 37 of 73 Figure 4-6.Detector base connections BSR-6155/MAR, BSR-6160/MAR and BSR-6157/MAR 37 / 73...
Page 38
Date 29/6/2021 Document number 921100409_09_002 Page 38 of 73 Figure 4-7.Connecting the manual call point (MCP) BSR-5136/MAR Figure 4-8.Connecting addressable siren BSR-5132/MAR Figure 4-9.Connection of input/output unit BSR-8120/MAR 38 / 73...
Page 39
Date 29/6/2021 Document number 921100409_09_002 Page 39 of 73 4.4.2 Connecting conventional sirens Figure4-10.Conventional sirens connection There are four outputs to the main board for conventional sirens connection marked as «SIR1», «SIR2», «SIR3» and «SIR4». Each output can supply a current up to 300mA and it is monitored for short-circuit and open circuit.
Page 40
Date 29/6/2021 Document number 921100409_09_002 Page 40 of 73 4.5 Panel network connections A network of panels can support up to 4 interconnected control panels. Each control panel owns a unique address. The master panel owns the address 1 and the subpanels have the addresses 2, 3 and 4. The interconnection wire must be twisted pair (2-core).
Page 41
Date 29/6/2021 Document number 921100409_09_002 Page 41 of 73 4.6 General connections diagram A theoretical general connections diagram is depicted below: Figure4-12.General connections diagram 41 / 73...
Page 42
Date 29/6/2021 Document number 921100409_09_002 Page 42 of 73 4.7 Other connections The following section contains information for other available connections in the control panel. For each of the following connection a separate cable must be used (don’t use multicore cables to connect multiple outputs).
Page 43
Date 29/6/2021 Document number 921100409_09_002 Page 43 of 73 adaptor set up the IP address of the control panel via Technician menu and connect the network cable to the corresponding RJ45 socket on the adaptor (figure 4-14). Printer: To connect a printer adaptor, disconnect batteries and mains power and place it on the corresponding connector on the CPU board (same position of figure 4-14).
Page 44
Date 29/6/2021 Document number 921100409_09_002 Page 44 of 73 5 Technician Menu The following chapter includes all information for commissioning a new installation of a BSR-100X Analogue Addressable Fire Alarm Panel. The technician menu contains a set of commissioning functions, parameters and other general settings and is code protected (access level 3).
Page 45
Date 29/6/2021 Document number 921100409_09_002 Page 45 of 73 Figure5-3.Technician menu diagram In the following sections a detailed description for every available option appears. 45 / 73...
Page 46
Date 29/6/2021 Document number 921100409_09_002 Page 46 of 73 5.1 Test Menu This submenu is used during periodic maintenance of the system to set the fire detection equipment in test mode in order to confirm functionality. The available options are the following on figure 5-4. WARNING! By enabling test mode to a control panel the system’s fire detection ability is inhibited until test mode is terminated.
Page 47
Date 29/6/2021 Document number 921100409_09_002 Page 47 of 73 5.1.4 Device LED Address “DEVICE LED ADDRESS” option starts a countdown procedure of 25 minutes while every connected fire detection device indicates its address by a special flashing pattern that is repeating. 3burst short flash 2 seconds gap number of flashes multiplied by tens (with 1s gap between)
Page 48
Date 29/6/2021 Document number 921100409_09_002 Page 48 of 73 Additional information for the selected points can be displayed by pressing the View Alarms key once. The additional information is “OPERATING HOURS” and “ALARM COUNTER” of the specific point. Figure5-10.Check point 2 5.2.2 Check loop communication “LOOP COMMUNICATION”...
Page 49
Date 29/6/2021 Document number 921100409_09_002 Page 49 of 73 5.2.5 Check voltage outputs “VOLTAGE OUTPUTS” will display the screen on the right, for the technician to select one of the 24V generic outputs for testing. During testing the selected output will switch off for 6 seconds and switch on again.
Page 50
Date 29/6/2021 Document number 921100409_09_002 Page 50 of 73 5.3 Setup menu This submenu contains a series of configuration options for almost every segment of the fire detection system. 5.3.1 Points ”POINTS” option will prompt for selecting a specific point address. First select the point’s loop and then its address.
Page 51
Date 29/6/2021 Document number 921100409_09_002 Page 51 of 73 The preset name of the point will be “POINT Y.XXX” where Y the point’s loop and XXX the point’s address. The preset zone of each point will be equal to its loop (e.g. point 3.025 zone will be zone 3). The first line, “CURRENT ADDRESS”...
Page 52
Date 29/6/2021 Document number 921100409_09_002 Page 52 of 73 5.3.4 Change point address This option may be used in order to change a specific point’s address, in purpose of replacement, adding new point or other modifications on the installation. This function will send a command to change the address of all connected devices to the selected loop.
Page 53
Date 29/6/2021 Document number 921100409_09_002 Page 53 of 73 choices are appeared NO/YES, if you select YES then by pressing the SIREN SILENCE button the output will stop. By selecting NO the output will stop only after a RESET. - Pre-alarm: Same choices with the alarm menu. - On a specific zone: Select task, delay (from NO up to 10 minutes) and YES or NO at SIREN SILENCE.
Page 54
Date 29/6/2021 Document number 921100409_09_002 Page 54 of 73 5.3.9 Panel Network “PANEL NETWORK” submenu contains the options listed on the screen on the right. Figure5-26.Panel network First option, “PANEL ADDRESS” will open an input window to configure the control panel’s address within the network of panels. Each address must be unique.
Page 55
Date 29/6/2021 Document number 921100409_09_002 Page 55 of 73 5.3.10 Loops “LOOPS” option displays the screen shown on the right. Via this selection screen, the technician can register / unregister loop circuits. Use up/down keys to navigate between the loops and right key to select or unselect activation.
Page 56
Date 29/6/2021 Document number 921100409_09_002 Page 56 of 73 5.3.13 Indication of points “INDICATION OF POINTS” option is used to enable or disable the red LED indicator blinking on the addressable points. Useful on areas (e.g. hotels) that LED blinking might bother inhabitants or other special events.
Page 57
Date 29/6/2021 Document number 921100409_09_002 Page 57 of 73 5.4.2 Change technician code “CHANGE TECH CODE” option will display the screen on the right, asking the technician to enter a new code for access level 3. After inputting the code, the panel asks to enter the new code again for confirmation.
Page 58
Date 29/6/2021 Document number 921100409_09_002 Page 58 of 73 The first option “ETHERNET PCB” is used to enable / disable the Ethernet adaptor. Enable the Ethernet adaptor only when a GR-8530 Ethernet adaptor card is installed into the panel. Figure5-43.Ethernet PCB Next option, “IP ADDRESS”...
Page 59
Date 29/6/2021 Document number 921100409_09_002 Page 59 of 73 5.4.8 Annual check date “ANNUAL CHECK DATE” option indicates the next scheduled maintenance date. Figure5-48.Annual check date 5.4.9 Reset defaults “RESET DEFAULTS” clears memory and restores all configurations back to factory default values. The only exceptions are certain hardware configurations: Loops (enabled/disabled), External PCB function, Ethernet PCB (enabled/disabled).
Page 60
Date 29/6/2021 Document number 921100409_09_002 Page 60 of 73 5.7 PC Communication The “PC COMMUNICATION” option is used to download/upload configurations from or to a PC via USB cable, running the BSR-100X software application. When selected, a confirmation message as the screen on the right will be displayed.
Page 61
Date 29/6/2021 Document number 921100409_09_002 Page 61 of 73 The menu design is similar to the corresponding panel’s menu. Although some functions can be made exclusively by using the Ethernet menu, (e.g. “CHANGE INFORMATION”). The following paragraph is describing the new options available to configure via web interface that were not present via the keypad.
Page 62
Date 29/6/2021 Document number 921100409_09_002 Page 62 of 73 6 Initial installation procedure The initial installation of the BSR-100X/MAR Analogue Addressable Fire Alarm systems comes with an advanced “tool” that automatically sets the address of each point in a loop, to save time and make installation easier.
Page 63
No faults, alarms or prealarms should be active and the control panel’s screen should display the message “SYSTEM READY”. Full access to the BSR-100X/MAR control panel’s programming options can be granted via the BSR-100X PC software application by Olympia Electronics. You can download the software directly by the official Olympia Electronics website for free: https://www.olympia-electronics.com/en/support/software See chapter 7 for further information.
Page 64
Date 29/6/2021 Document number 921100409_09_002 Page 64 of 73 7 BSR-100X PC software application 7.1 Programming the panel In order to connect the BSR-100X/MAR control panel to a PC, a Mini-USB 2.0 cable will be needed. The Mini-USB port on the control panel is located on the back side of the CPU board, above the lock mechanism.
Page 65
Date 29/6/2021 Document number 921100409_09_002 Page 65 of 73 When the BSR-100X/MAR control panel is detected, the message “Ready” will be displayed on the bottom line of the “Synchronize with Panel window” To receive control panel configuration file, click on “Receive”...
Page 66
Date 29/6/2021 Document number 921100409_09_002 Page 66 of 73 Now proceed with configuring other parameters, such as detector alarm limits and names. Click on a loop entry on the left column. All registered points in this loop, appear on the right section of the screen. When an entry is selected, its data is displayed on a form below: Double click on a point to edit name and parameters.
Page 67
Date 29/6/2021 Document number 921100409_09_002 Page 67 of 73 After finishing with the configurations (names, zones, tasks, behavior etc.), save a copy of the configuration file: File > Save As Keep this configuration file copy on a safe location which can be later used to restore this data. To transfer the new configuration file, go to: Panel Communication >...
Page 68
Date 29/6/2021 Document number 921100409_09_002 Page 68 of 73 Calculation of the required section of the cable: Select the length of the cable. On the left column the results are shown. At the top of the screen there are bars changing color depending on the result and at the bottom of the screen there is a detailed table with the results based on the selections we made.
Page 69
Date 29/6/2021 Document number 921100409_09_002 Page 69 of 73 8.2 Functions Similar to BSR-1001-2-4/MAR the BSR-1000/MAR has the same functionality as far as the indicators, screen and keypad concerns, as well as the Menu structure.The only difference is some functions limitation, i.e. the screen on the right is shown on menus that repeaters cannot access, preventing wrong actions.
Page 70
Date 29/6/2021 Document number 921100409_09_002 Page 70 of 73 8.5.2 Panel network detection In order to complete panel network setup, electrical connection to the mains network as well as connection between the panels with the RS-485 network should be carried out. Then address 1 is set to master panel from “TECHNICIAN MENU”...
Page 71
Date 29/6/2021 Document number 921100409_09_002 Page 71 of 73 9 Technical Characteristics – Properties BSR-1001/MAR BSR-1002/MAR BSR-1004/MAR Analogue Addressable Analogue Addressable Analogue Addressable Description Fire Alarm Panel Fire Alarm Panel Fire Alarm Panel 1 Loop / 128 Zones 2 Loops / 128 Zones 4 Loops / 128 Zones Mains power input 220-240VAC/50-60Hz...
Page 72
Date 29/6/2021 Document number 921100409_09_002 Page 72 of 73 Mains input: 4A/250V (Fast) TR5 – non replaceable Fuse type Battery: 900mA self resettable – non replaceable Operating -5 to 40 °C temperature range Relative humidity Up to 95% non-condensing Construction ABS –...
Page 73
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.