HS2750 and HS5500 Installation & Operating Instructions IN115 RevA v1 3 Saber Way, Ward Hill, MA 01835 | radonaway.com...
Page 2
2. WARNING! Check voltage at the blower to ensure it corresponds with nameplate. See Vapor Intrusion Application Note #AN001 for important information on VI Applications. RadonAway.com/vapor-intrusion 3. WARNING! Normal operation of this device may affect the combustion airflow needed for safe operation of fuel burning equipment.
Under no circumstances should water be allowed to be drawn into the inlet of the HS2750 and HS5500 Blowers as this may result in damage to the unit. The HS2750 or HS5500 Blower should be mounted at least 5 feet above the slab penetration to minimize the risk of filling the Blower with water in installations with occasional high water tables.
1.7 SLAB COVERAGE The HS2750 or HS5500 Blower can provide coverage of well over 1000 sq. ft. per slab penetration. This will, of course, depend on the sub-slab aggregate in any particular installation and the diagnostic results. In general, sand and gravel are much looser aggregates than dirt and clay.
2.1 MOUNTING Mount the HS2750 or HS5500 Blower to the wall studs, or similar structure, in the selected location with (4) 1/4” x 1 1/2” lag screws (not provided). Ensure the HS2750 or HS5500 Blower is both plumb and level.
Page 7
RadonAway®. The Blower must be returned (at Owner’s cost) to the RadonAway® factory. Any Blower returned to the factory will be discarded unless the Owner provides specific instructions along with the Blower when it is returned regardless of whether or not the Blower is actually replaced under this warranty.