MDT KNX SCN-RT1UP.01 Technical Manual page 22

Room temperature controller
Hide thumbs Also See for KNX SCN-RT1UP.01:
Table of Contents

Advertisement

Technical Manual – Room Temperature Controller SCN-RT1
4.4.2.7 Operating mode after reset
The following settings are available at the ETS-Software:
Figure 11: Operating mode after reset
The following chart shows the dynamic range for this parameter:
ETS-text
Operating mode after reset
Table 23: Operating mode after reset
This parameter defines the operating mode, which shall be adjusted after a bus power return. The
controller can start with the comfort mode or with the standby mode. In both cases, the
parameterized set point will be restored. By using setting "Hold old state and set point", the
controller restores the old operating mode and the set point, which was active before the reset. It
must be pointed out, that the controller has no settings in its memory in case of an initial operation.
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
22
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
▪ Comfort with
parameterized set point
▪ Standby with parameterized
set point
▪ Hold old state and set point
comment
Adjustment, which operating mode shall
be switched on after a bus power return