Technical Manual – Room Temperature Controller SCN-RT1
4.4.2.5 Priority of the operating modes
The following settings are available at the ETS-Software:
Figure 10: Priority of the operating modes
The chart shows the dynamic range of the priority of the operating modes:
ETS-text
Priority
Table 16: Priority of the operating modes
The setting of the priority enables to adjust which operating mode shall be switched primarily when
more than one operating mode is switched on. At the priority of Frost/Comfort/Night/Standby, the
comfort mode will be switched on even if comfort and night is switched on to the same time. The
night mode will only be active, when the comfort mode is switched off. now the controller changes
automatically to the night mode.
4.4.2.6 Operating mode switchover
There are 2 possibilities for the switchover of the operating modes: On the one hand the operating
modes can be switched on by their 1 Bit communication object and on the other hand by a 1 Byte
object (from Version 1.2).
The selection of the operating modes by their 1 Bit communication object occurs via a direct
selection of their individual communication object. With consideration of the adjusted priority, the
operating mode, which was selected via the 1 Bit communication object, is switched on or off. When
all operating modes are switched off, the controller changes to the standby mode.
Example:
The priority was set as
Operating mode
Comfort
Night
1
0
0
1
0
0
0
0
1
0
1
1
Table 17: Example switchover of the operating modes via 1 Bit
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
19
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
▪ Frost/Comfort/Night/Standby
▪ Frost/Night/Comfort/Standby
Frost/Comfort/Night/Standby.
Frost-/ Heat protection
0
0
1
0
1
0
comment
Adjustment of the priority of the
operating modes
adjusted operating mode
Comfort
Night
Frost-/Heat protection
Standby
Frost-/Heat protection
Comfort