MDT KNX SCN-RT1UP.01 Technical Manual page 18

Room temperature controller
Hide thumbs Also See for KNX SCN-RT1UP.01:
Table of Contents

Advertisement

Technical Manual – Room Temperature Controller SCN-RT1
4.4.2.1 Operating mode Comfort
The operating mode comfort is the reference mode of the controller. The temperature reduction at
the operating modes night and standby refer to the setpoint of the comfort mode. When a room is
used, the operating mode comfort should be activated. The configured setpoint, the "basic comfort
setpoint, is valid for the heating process if the controller was set as heating & cooling (described at
4.4.7).
The chart shows the relevant 1-Bit communication object:
Number
Name
11
Mode comfort
Table 13: Communication object operating mode comfort
4.4.2.2 Operating mode Night
The operating mode night shall cause a significant decrement of the temperature, for example at
night or at the weekend. The reduction can be programmed freely and refers to the basic comfort
setpoint. If you have programmed a reduction of 5K and a basic comfort setpoint of 21°C, the
setpoint for the night mode will be 16°C.
The chart shows the relevant 1-Bit communication object:
Number
Name
12
Mode night
Table 14: Communication object operating mode night
4.4.2.3 Operating mode Standby
When nobody is in the room, the operating mode standby is used. This operating mode shall cause a
low reduction of the temperature. So the room can be heated up fast again.
The value for the reduction can be programmed freely and refers to basic comfort setpoint. If you
have adjusted a reduction of 2K and a basic comfort setpoint of 21°C, the setpoint for the operating
mode standby will be 19°C.
The standby mode cannot be activated by a certain communication object. It gets activated, when all
operating modes are switched off.
4.4.2.4 Operating mode Frost/Heat protection
The operating mode frost protection gets activated, when the controller type was set as heating. The
heat protection gets activated, when the controller type was set as cooling. When the controller type
is set to heating and cooling, the combined operating mode frost-/ heat protection is activated.
This operating mode causes an automatically switch on of heating or cooling, when a parameterized
is exceeded or the temperature falls below a parameterized temperature. At this operating mode,
the temperature is set as absolute value. You should activate this function if you are longer absent
and the temperature must not fall below a specific value or exceed a specific value.
The chart shows the relevant 1-Bit communication objects:
Number
Name
13
Mode frost protection
13
Mode heat protection
13
Mode frost/heat protection
Table 15: Communication object operating mode frost/heat protection
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
18
Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Length
Usage
1 Bit
Activation of the operating mode comfort
Length
Usage
1 Bit
Activation of the operating mode night
Length Usage
1 Bit
Activation of the operating mode frost protection
1 Bit
Activation of the operating mode heat protection
1 Bit
Activation of the operating mode frost/heat
protection

Advertisement

Table of Contents
loading

This manual is also suitable for:

Knx scn-ts1up.01Knx scn-rt1upe.01Knx scn-rt1ape.01

Table of Contents