INSTALLATION MANUAL
STANDARD ECM
MODULAR MULTI-POSITION
AIR HANDLERS
MODELS: ME SERIES - 208/230 V - 1 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
DUCT WORK AND CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRIC HEATER INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . 6
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LOW VOLTAGE CONTROL CONNECTIONS . . . . . . . . . . . . . . . . . . 7
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Return Air Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Coil and Air Handler Attachment Details . . . . . . . . . . . . . . . . . . . . . . . 3
Gasket Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensions and Duct Connection Dimensions . . . . . . . . . . . . . . . . . . 4
Typical Horizontal Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Duct Work Transition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Line Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical and Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . . 8
Electrical Data - Cooling Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SECTION I: GENERAL
The ME modular air handler series provides the flexibility for installation
in any position. This unit may be used for upflow, downflow, horizontal
right, or horizontal left applications.
These units may be located in a closet, utility room, attic, crawl space,
or basement. These versatile models may be used for cooling or heat
pump operation with or without electric heat or indoor coil.
Top or side power and control wiring, color coded leads for control
wiring, and electric heaters all combine to make the installation easy
and minimize installation cost.
Electric heat kits are available as field installed accessories. Single
phase kits are available from 2.5 kW to 25 kW. 208-230 volt three
phase kits are available from 10 kW to 25 kW.
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
Johnson Controls Ducted Systems
LIST OF SECTIONS
UNIT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
AIR SYSTEM ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TYPICAL THERMOSTAT CONNECTIONS . . . . . . . . . . . . . . . . . . . 14
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
TYPICAL THERMOSTAT CONNECTIONS . . . . . . . . . . . . . . . . . . . 17
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LIST OF FIGURES
Blower Speed Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Duct Static Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Outdoor - ECM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring Diagram - Three Phase Heat Kits . . . . . . . . . . . . . . . . . . . . . 16
ECM Blower Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
LIST OF TABLES
Airflow Data (CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property
damage.
FIRE OR ELECTRICAL HAZARD
Failure to follow the safety warnings exactly could result in serious
injury, death or property damage. A fire or electrical hazard may result
causing property damage, personal injury or loss of life.
The air handler area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-
ers or other cleaning tools.
2. Soap powders, bleaches, waxes or other Cleaning compounds;
plastic items or containers; gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids or other volatile fluid.
3. Paint thinners and other painting compounds.
4. Paper bags, boxes or other paper products
Never operate the air handler with the blower door removed. To do so
could result in serious personal injury and/or equipment damage.
WARNING
!
WARNING
!
5724452-UIM-A-0619
ISO 9001
Certified Quality
Management System

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ME Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls ME Series

  • Page 1: Table Of Contents

    AIR HANDLERS ISO 9001 Certified Quality MODELS: ME SERIES - 208/230 V - 1 PHASE Management System LIST OF SECTIONS GENERAL ..........1 UNIT DATA .
  • Page 2: Safety

    Air Handler Voltage Normal Operating Voltage Range and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation. 208-230-1-60 187-253 1. Rated in accordance with ARI Standard 110, utilization range “A”. Johnson Controls Ducted Systems...
  • Page 3: Typical Installation

    Apply foam gasket over the air handler and coil mating seams on the interior of both unit sides and back. Refer to Figure 4. Slide the coil into the housing, and install the coil access panel and coil filter door. Johnson Controls Ducted Systems...
  • Page 4: Gasket Location

    21-1/2 17-1/2 16-1/2 16-1/2 ME12B 21-1/2 17-1/2 16-1/2 16-1/2 7/8 (1/2) ME12C 22-1/2 1-3/8 (1) 7/8 (1/2) ME14D 22-1/2 24-1/2 23-1/2 23-1/2 1-23/32 (1-1/4) ME16C 22-1/2 ME20D 22-1/2 24-1/2 23-1/2 23-1/2 1. Dimensions are in inches. Johnson Controls Ducted Systems...
  • Page 5: Duct Work And Connections

    For suspension of these units in horizontal applications, it is recom- mended to use angle steel support brackets with threaded rods, sup- porting the units from the bottom, at the locations shown in Figure 6. FIGURE 7: Duct Attachment Johnson Controls Ducted Systems...
  • Page 6: Electric Heater Installation

    Caution must be used when sizing aluminum rather than copper conductors, as aluminum conductors are rated for less current than copper conductors of the same size. Equipment should never be operated without a filter. Johnson Controls Ducted Systems...
  • Page 7: Low Voltage Control Connections

    1, and the highest speed is 5. The air handler comes factory wired with the electric heat kit connected to tap 5 for the heating speed, and the Yellow cooling/heat pump lead connected to tap 4 for the cooling/heat pump heating speed. Johnson Controls Ducted Systems...
  • Page 8: Physical And Electrical Data - Cooling Only

    2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect and breaker jumper bar 3. 6HK3 = 3-phase with terminal block connectors only. 6HK4 = 3-phase with service disconnect Johnson Controls Ducted Systems...
  • Page 9: Default Blower Speeds For Fer Compliance - Electrical Heat Only

    2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect and breaker jumper bar 3. 6HK3 = 3-phase with terminal block connectors only. 6HK4 = 3-phase with service disconnect 4. For different power distributions, see the conversion table above. Johnson Controls Ducted Systems...
  • Page 10: Electric Heat Performance Data: 208/230-1-60 And 208/230-3-60

    3. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. Refer to the latest edition of the National Electrical Code or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing. Johnson Controls Ducted Systems...
  • Page 11: Electrical Data For Multi-Source Power Supply: 208/230-1-60

    3. The 20 kW and 25 kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard. Single source power MCA and MOP require- ments are given here only for reference if used with field installed single point power modification. Johnson Controls Ducted Systems...
  • Page 12: Electrical Data For Multi-Source Power Supply: 208/230-3-60

    Low (1) High (5) 1360 1334 1291 1253 1207 1172 1076 Medium High (4) 1274 1242 1202 1157 1109 1040 1000 ME12C CM61C Medium (3) 1060 1022 Medium Low (2) Low (1) Continued on next page Johnson Controls Ducted Systems...
  • Page 13 For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50” w.c. esp. Airflow data shown is from testing performed at 230 V. AE units use a standard ECM constant torque motor, and there is minimal variation of airflow at other distribution voltage values. Johnson Controls Ducted Systems...
  • Page 14: Maintenance

    SECTION XII: TYPICAL THERMOSTAT CONNECTIONS Wout FIELD INSTALLED JUMPER IF REQUIRED Wout FIELD INSTALLED JUMPER IF SINGLE STAGE THERMOSTAT IS USED. FIELD INSTALLED JUMPER IF REQUIRED A1259-001 FIGURE 12: Typical Thermostat Wiring Diagram - Single Stage Outdoor - ECM Johnson Controls Ducted Systems...
  • Page 15: Wiring Diagram

    RLY - RELAY SEQ2 SEQ3 SEQ1 USE COPPER CONDUCTORS ONLY. IF ALUMINUM CONDUCTORS ARE PRESENT, ALL APPLICABLE LOCAL AND NATIONAL CODES MUST BE FOLLOWED. 5724441-UWD-A-0219 FIGURE 13: Wiring Diagram - Standard ECM - Single Phase Heat Kits Johnson Controls Ducted Systems...
  • Page 16: Wiring Diagram - Three Phase Heat Kits

    YELLOW BROWN YELLOW SD 2 BLACK WHITE BLACK BLUE BLUE BLUE PURPLE YELLOW YELLOW RED / WHITE RED / WHITE BLACK SD 1 BLACK BLACK BLACK 5175906-UWD-A-0216 FIGURE 14: Wiring Diagram - Three Phase Heat Kits Johnson Controls Ducted Systems...
  • Page 17: Typical Thermostat Connections

    XFORMER 6HK*6501506 HEATER KIT: "G" CALL ENERGIZES BLOWER FOR "Y1" SPEED. BLACK BLOWER MOTOR WIRE IS FOR ELECTRIC HEAT SPEED. A1260-001 FIGURE 15: Typical Thermostat Wiring Diagram - 2 Stage Heat Pump with ECM Blower Motor Johnson Controls Ducted Systems...
  • Page 18 5724452-UIM-A-0619 NOTES Johnson Controls Ducted Systems...
  • Page 19: Start Up Sheet

    Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature (Check all that apply) Other Jumpers HUM STAT AC/HP CONT FAN Continued on next Page Johnson Controls Ducted Systems...
  • Page 20 Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Subject to change without notice. Published in U.S.A 5724452-UIM-A-0619 Copyright © 2019 by Johnson Controls. All rights reserved. Supersedes: 5443671-UIM-B-0419 York International Corp. 5005 York Drive...