FAN FILTER UNIT - HIGH EFFICIENCY
INSTALLATION & SERVICE INSTRUCTIONS
Filter/Motor Indicator LED (FL/ML) – BTR
Sample line string below:
FFU-HE/24/48/BTR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB///ML/FL/WPF/PL-AL///PL-MILL//
LED Operation
Option
Code
Filter LED
FL
Motor
ML
LED
Installation
STEP 1: Remove BTR filter from box by following the instructions found on page 23 of this installation manual.
STEP 2: Take LED cable assembly out of FFU-HE Plenum
LED
Action
Color
Green
None
Yellow
Change Filter
Green
None
Red
Troubleshoot Motor
Notes
Indicates normal operation until filter pressure drop exceeds calibrat-
ed pressure drop (factory set at 1.5x clean filter pressure).
Indicates filter pressure drop has exceeded calbirated setting (factory
set at 1.5x clean filter pressure.
Indicates normal motor operation when the static pressure is above
0.2" w.g.
Indicates motor is not in operation, and that unit static pressure is
below 0.2" w.g.
Cable Assembly