INSTALLATION

HX CS cold store air curtains are designed to be surface mounted inside a building and located
horizontally over the doorway between the loading bay and the cold store which is maintained at
minus temperatures. It must not be installed outside of the building.
7.1
Location
Mount the air curtain above the doorway, with:
the discharge grille not more than 4m above floor level
at least 100mm clearance above the air curtain, see Fig 1
with the back edge of the hanging bracket 100mm from the doorway,
so the air curtain can swivel, see Fig 1, Figs 2a and 2b.
Beware of doorway top edges, structural beams, door opening/closure
devices, etc., which may interfere with the air stream and affect the location of
the unit.
60
NOTE: For the air curtain to work well the width of the open doorway should be less than the
effective width of the airstream, see Table 1.
T9901108-1-1 UK
200
340
95
20° max.
Fig 2a
Fig 1
200
60
340
95
20° max.
Fig 2b
100mm
4000mm
Page | 6