Tools Required; Installation (Horizontal Units) - Thermoscreens CS 1000 Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

6.

TOOLS REQUIRED

The following tools are required for installation:
Flat blade screwdrivers
Pozi head screwdrivers
10mm and 19mm spanners
Adjustable spanner
7.

INSTALLATION (HORIZONTAL UNITS)

The air curtain is designed to be surface mounted inside a building and located horizontally over the
doorway. It must not be installed outside of the building.
7.1
Location
Mount the air curtain above the doorway, with:
the discharge grille not more than 4m above floor level
at least 100mm clearance above the air curtain, see Fig 1
with the back edge of the hanging bracket 100mm from the doorway,
so the air curtain can swivel, see Fig 1, Figs 2a and 2b.
Beware of doorway top edges, structural beams, door opening/closure
devices, etc., which may interfere with the air stream and affect the location of
the unit.
Fig 2a
60
NOTE: For the air curtain to work well the width of the open doorway should be less than the
effective width of the airstream, see Table 1.
T9901150-1-1 UK
200
340
95
20° max.
Electric drill
Equipment for working at height
Appropriate lifting equipment
Hacksaw
200
60
340
100mm
4000mm
Fig 1
Fig 2b
95
20° max.
Page | 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs 1500Cs 2000

Table of Contents