Installation - Thermoscreens Compact 2 Series Installation, Operation And Maintenance Instructions

Surface mounted
Table of Contents

Advertisement

7

Installation.

The air curtain is designed to be located horizontally over a doorway. It must not be installed outside of
the building.
7.1
Location
Mount the air curtain above and as close to the doorway as
possible, with:
air curtain mounted up to a maximum 3.0m. For exposed
locations, 2.5m is the recommended mounting height.
at least 100mm clearance (air gap) above electric/water
heated air curtains, see Fig 1
Beware of doorway top edges, structural beams, door
opening/closure devices, etc., which may interfere with the air
stream and affect the location of the unit.
NOTE: For the air curtain to work well the width of the open doorway should be less than the length
'A' of the air curtain, see Appendix 1.
7.2
Wall Fixing
:
NOTE
Use suitable wall fixing bolts (not supplied) to fix the unit to the wall, taking into account the
type of wall and the weight of the unit (see Section 3: Specifications). For wall mounting, if
required, front ceiling rail from top of the air curtain may be removed.
Step 1
Fix two wall brackets above door opening with
minimum B and maximum C dimensions ensuring
minimum distance between brackets C
(see Appendix 1A). Ensure brackets are level
with each other.
Step 2
Angle air curtain over doorway and place outer
edge of discharge grille on lower channels of both
wall brackets.
T9901120-1-2 UK
Fig 1
0
0
.
min
Fig 2
Fig 3
C
B
Page | 6