Test Run - Toshiba RAV-HM301U1TP-E Installation Manual

Hide thumbs Also See for RAV-HM301U1TP-E:
Table of Contents

Advertisement

To find an indoor unit's position from its address
1
Push and hold menu button and [
] setting button simultaneously for 10 seconds or more.
(E.g.) A unit number 1-1 is indicated on the LCD of the remote controller. The indicated number shows the line
(system) address and indoor unit address of the unit.
2
When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of
other connected units appears each time you push the [
3
Push the ON/OFF button, return to the normal mode.
37-EN
] [
] buttons.
– 19 –
9

Test run

Before test run
Before turning on the power supply, carry out the
following procedure.
1) By using 500V-megger, check that resistance of
1MΩ or more exists between the terminal block
1 to 3 and the earth (grounding).
If resistance of less than 1MΩ is detected, do not
run the unit.
2) Check the valve of the outdoor unit being opened
fully.
To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
Execute a test run
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner's Manual.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than
the test run because it applies an excessive load
to the devices.
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
4
3
3
1
2
1
Push and hold OFF timer button and [
setting button simultaneously for
10 seconds or more. [TEST] is displayed
on the display part and the test run is
permitted.
2
Push ON/OFF button.
3
Push menu button to select the operation
mode. Select [
Cool] or [
Heat] with
[
] [
] setting button.
• Do not run the air conditioner in a mode other
than [Cool] or [Heat].
• The temperature setting function does not work
during test run.
• The check code is displayed as usual.
4
After the test run, push OFF timer button to
stop a test run.
([TEST] disappears on the display and the
air conditioner enters the normal stop mode.)
]
38-EN