2
Each time [
] [
] setting button is
pushed, indoor unit numbers in the group
control change cyclically. Select the
indoor unit to change settings for.
• The fan of the selected indoor unit runs and the
louvers start swinging. The indoor unit can be
confirmed for which to change settings.
3
Push OFF timer button to confi rm the
selected indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
] fl ash. Change Code No. [
[
] [
] setting button.
5
Push the menu button to make Set data
[
] fl ash. Change Set data [
with [
] [
] setting button.
6
Push OFF timer button to complete the set
up.
To change other settings of the selected
4
indoor unit, repeat from Procedure
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode)
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit, repeat
1
from Procedure
.
33-EN
To secure better effect of
heating
When it is diffi cult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
6
7
(
).
Specify [06] for the Code No. in Procedure
5
For the Set data in Procedure
of shift value of detection temperature to be set up
from the following table.
Set data
Detection temperature shift value
0000
No shift
0001
+1°C
+2°C
0002
(Factory default)
] with
0003
+3°C
0004
+4°C
]
0005
+5°C
0006
+6°C
Filter sign setting
.
According to the installation condition, the fi lter sign
term (Notifi cation of fi lter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
7
(
).
Specify [01] for the Code No. in Procedure
5
For the Set data in Procedure
of fi lter sign term from the following table.
Set data
Filter sign term
0000
None
0001
150 H
2500 H
0002
(Factory default)
0003
5000 H
0004
10000 H
• The filter sign may be unavailable depending on the
remote controllers.
– 17 –
Remote controller sensor
The temperature sensor of the indoor unit senses
room temperature usually. Set the remote controller
sensor to sense the temperature around the remote
controller.
Select items following the basic operation procedure
1
2
3
(
Specify [32] for the Code No. in Procedur
Select the following data for the Set data in
Procedure
4
.
, select the Set data
Set data
0000
0001
When
flashes, the remote controller sensor is
defective.
Select the Set data [0000] (not in use) or replace the
remote controller.
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change to
TCC-Link.
Follow to the basic opreration procedure
1
2
3
(
Specify [FC] for the Code No. in Procedure
Select the Set data [0000] (TCC-Link) in Procedure
5
.
Set data
0000
0004
4
.
Fan speed setting when
, select the Set data
thermostat-OFF in cooling
mode
Set the fan speed when the room temperature reaches
the set temperature in the cooling mode.
Follow to the basic opreration procedure
1
2
3
(
Specify [9A] for the Code No. in Procedure
Select the following data for the Set data in
Procedure
Set data
0000
0001
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic opreration procedure
1
(
4
5
6
7
).
Specify [d1] for the Code No. in Procedure
4
.
Select the following data for the Set data in
Procedure
5
.
Remote controller sensor
Not in use (Factory default)
In use
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
The following functions require a connection with
the RBC-AMTU
controller. For details, refer to the manual included with
4
5
6
7
).
the remote controller.
4
• Individual unit selection during group operation
.
• Individual setting of louver position (wind direction)
• Swing type setting
• Louver lock (no swing) setting
• Energy saving operation (Power saving operation)
Communication type
• Notification of filter cleaning time
TCC-Link
TU2C-Link (Factory default)
The following functions can be used with this model.
Refer to the Service Manual for more information.
• Rotation / backup operation
• Free cooling
• Secondary heating
• Power shift
4
5
6
7
).
4
.
5
.
Fan speed when thermostat-OFF
in cooling mode
Remote controller setting
Extremely low speed (UL)
(Factory default)
8°C operation
2
3
4
5
6
7
).
4
.
5
.
Set data
8°C Operation setting
0000
None (Factory default)
0001
8°C Operation setting
Installing optional parts
Information
and RBC-AMSU
remote
Others
34-EN