137 - 145
Adaptive superheat control PID parameters
In case an electronic expansion valve is used (configured in parameter
controlled by an adaptive PID controller. This parameters define proportional, integral and differential part of
the controller. Also the stability is evaluated continuously. In case the controller is becoming unstable the
controller parameters are adapted.
146
Adjust opening threshold
In case the compressor speed is changing the EXV must follow very fast to keep a stable superheat. This is
done by a feedforward control reacting on regular EXV controller. If the increasing in speed is above the value
defined in this parameter, the feedforward control is activated. The value is set in percent of the maximum
speed rate in capacity control
147
Adjust opening factor
The additional opening of the EXV done by feed forward control is calculated by the difference between the
increasing in speed and the threshold configured in parameter
between the valve opening (0 – 100 %) and the acceleration rate ( 0 – 100% of
control) can be done by this parameter.
148
Oil return speed
To guarantee that no oil is not settling in the evaporator when running a variable speed compressor on low
speed for a longer time an oil return should be forced after a certain time. The speed of the compressor when
running in oil return mode is defined by this parameter.
149
Oil return threshold
When the compressor stays below the speed configured in this parameter for a duration longer than the time
configured in parameter
150
Oil return duration
During an oil return the Compressor is running with speed configured in parameter
for a time set by this parameter.
151
Oil return threshold duration
The time the compressor is running with a speed below the value configured in parameter
threshold
is accumulated. When the compressor speed rises above the threshold the duration timer is paused.
If the speed drops again below the threshold level the timer continuous running. The timer is only reset if an
oil return is triggered or a second timer running in parallel (also when the speed is above the threshold) expires.
152
Capacity control Kp
If a variable speed compressor is used
temperature / capacity control is done by a PI controller
control
Ki). The compressor speed (capacity) is controlled by a PI controller. This parameter defines the
proportional part.
153
Demand defrost trigger correction
When a variable speed compressor is used the compressor speed is included in the defrost detection
algorithm. By increasing this factor the impact of the compressor speed on the delta detection gets more heavy
(see Parameter 52).
154
Compressor Code
In a variable speed application the package of compressor, drive and envelope has to be set by this parameter.
According to this code the drive is initialized.
155
Digital input door
The corresponding digital input (DI 1 or DI 2) for a door contact can be set by this parameter.
156
Contact logic door
The door input can be configured with a normally open or normally closed contact logic.
157
Restart delay open door
If the door is open the cooling is stopped immediately and after the door is closed cooling is restarted. In case
the door stays open for a period longer than the time defined by this parameter, cooling is restarted even when
the door is still open.
„Door open" alarm delay
158
If the door is open the cooling is stopped immediately. In case the door stays open for a period longer than the
time defined by this parameter an Alarm is triggered.
Proprietary and confidential – Do not copy or distribute without permission from Emerson Climate Technologies GmbH
Technical Information
135 Speed rate capacity control.
150 Oil return duration
(121
Compressor command type
146 Adjust opening
an oil return is triggered.
152
Capacity control Kp
68 Valve
type) the superheat is
threshold. An adjustment
135 Speed rate capacity
148 Oil return speed
149 Oil return
is set to Drive) the
and
124
Capacity
32/42