4.6 Quick Logic

The 'Quick Logic' feature allows the user to input up to 4 logic equations (E1 to E4) in text format. Equations can
be entered using Reydisp or at the relay fascia.
Each logic equation is built up from text representing control characters. Each can be up to 20 characters long.
Allowable characters are:
0, 1, 2, 3, 4, 5, 6, 7, 8, 9
( )
!
.
^
+
En
In
Ln
On
Vn
Example Showing Use of Nomenclature
E1= ((I1^V1).!O2)+L1
Equation 1 = ((Binary Input 1 XOR Virtual I/O 1) AND NOT Binary Output 2) OR LED 1
When the equation is satisfied (=1) it is routed through a pick-up timer (En Pickup Delay), a drop-off timer (En
Dropoff Delay), and a counter which instantaneously picks up and increments towards its target (En Counter
Target).
The counter will either maintain its count value En Counter Reset Mode = OFF, or reset after a time delay:
En Counter Reset Mode = Single Shot: The En Counter Reset Time is started only when the counter
is first incremented (i.e. counter value = 1) and not for subsequent counter operations. Where En
Counter Reset Time elapses and the count value has not reached its target the count value is reset to
zero.
En Counter Reset Mode = Multi Shot: The En Counter Reset Time is started each time the counter is
incremented. Where En Counter Reset Time elapses without further count increments the count value
is reset to zero.
Chapter 1 - Page 30 of 38
Digit
Parenthesis
'NOT' Function
'AND' Function
'EXCLUSIVE OR' Function
'OR' Function
Equation (number)
Binary Input (number)
'1' = Input energised, '0' = Input de-energised
LED (number)
'1' = LED energised, '0' = LED de-energised
Binary output (number)
'1' = Output energised, '0' = Output de-energised
Virtual Input/Output (number)
'1' = Virtual I/O energised, '0' = Virtual I/O de-energised